MIS-2839
FIGURE 27
Control Connector Motor Half
* Suggested mating connector
Housing — AMP 350809-1
Contact — AMP 350537-1
**
WARNING
–
Applying 240VAC line input with
PIN 1 to PIN 2 jumper in place will permanently
damage unit!
Power Connector Motor Half
Mode of
Operation
OFF
Continuous
Blower
(Ventilation
Mode)
Part Load
Cooling
("Y1-Y2"
Jumper
Removed)
Full Load
Cooling
Dehum.
Mode
(when
equipped)
Part Load
Heat Pump
("Y1-Y2"
Jumper
Removed)
Full
Load Heat
Pump
Heat Pump
Full Load w/
1st Bank of
Elec. Heat
Heat Pump
Full Load w/
1st & 2nd
Bank of Elec.
Heat
Emergency
Heat Mode
Thermostat
24 VAC
Input
Signals
—
"G"
"G", "Y1"
"G",
"Y1","Y2"
"D"
"G", "B",
"Y1"
"G", "B",
"Y1", "Y2"
"G", "Y1",
"Y2", "B",
"W1". "W2"
"G", "Y1", "Y2",
"B", "W2",
"W3"
"G",
"W2", "W3"
Pin #1
24 VAC "C" (Common) Signal, Always Energized
Pin #2
X
Pin #3
24 VAC "C" (Common) Signal, Always Energized
Pin #4
Not Used
Pin #5
Not Used
Pin #6
X
X
X
X
X
X
X
Pin #7
Not Used
Pin #8
Not Used
Pin #9
X
X
X
X
Pin #10
Not Used
Pin #11
Not Used
Pin #12
24 VAC Hot "R" Signal, Always Energized
Pin #13
X
X
X
Pin #14
X
X
X
X
Pin #15
X
X
X
X
X
X
X
X
X
Pin #16
Not Used
Power Connector
PWB Header
AMP 1-350945-0
PIN
Description
1
Jumper Pin 1 to Pin 2 for
120VAC Line Input Only **
2
3
Chassis Ground
4
AC Line
5
AC Line
TABLE 8
Troubleshooting ECM
TM
Indoor Blower Motors