Manual 2100-742A
Page
40 of 54
TABLE 11
Cooling Pressure – Balanced Climate Airflow
Air Temperature Entering Outdoor Coil °F
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operating charge being in the system, the charge should be removed and system evacuated and recharged to serial plate
charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See
Condenser Fan Operation
on page 27.
* Operating at these conditions would be outside the compressor operating envelope and is not recommended.
Model
Return Air Temp
(DB/WB)
Pressure
75
80
85
90
95
100
105
110
115
120
125
130
Q24H4
75/62
Suction Pressure
Head Pressure
116
291
119
312
122
333
124
355
127
378
129
402
131
426
133
451
135
478
136
505
138
532
140
567
80/67
Suction Pressure
Head Pressure
125
299
128
320
130
341
133
364
136
388
138
412
140
437
142
463
144
490
146
518
148
546
149
581
85/72
Suction Pressure
Head Pressure
129
309
132
331
135
353
138
377
140
401
143
426
145
452
147
479
149
507
151
536
153
565
155
602
Q30H4
75/62
Suction Pressure
Head Pressure
117
305
120
307
122
350
124
373
127
397
129
422
131
447
133
473
134
500
136
527
137
554
139
588
80/67
Suction Pressure
Head Pressure
125
313
128
336
131
359
133
383
136
408
138
433
140
459
142
485
144
512
145
540
147
569
149
603
85/72
Suction Pressure
Head Pressure
130
324
133
347
135
372
138
396
140
422
143
448
145
475
147
502
149
530
151
559
152
588
154
625
Q36H4
75/62
Suction Pressure
Head Pressure
125
379
125
384
126
392
127
404
128
420
130
439
131
462
133
490
135
520
138
555
140
593
--*
80/67
Suction Pressure
Head Pressure
134
389
134
394
135
402
136
414
137
431
139
451
140
474
142
502
145
534
149
569
150
608
--*
85/72
Suction Pressure
Head Pressure
138
402
139
407
139
416
140
429
142
446
143
466
145
491
147
520
150
552
152
589
155
629
--*