TABLE 20
Electrical Specifications – Q**H4D Series
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
The “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION:
When more than one (1) field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Model
Rated
Volts &
Phase
No. Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
Q24H4DA0Z
DA05
230/208-1
1
1
24
50
35
50
8
8
10
10
Q24H4DB0Z
DB06
DB09
230/208-3
1
1
1
16
34
43
20
35
45
12
8
8
12
10
10
Q24H4DC0Z
DC06
DC09
460-3
1
1
1
9
18
23
10
20
25
14
12
10
14
12
10
Q30H4DA0Z
DA05
230/208-1
1
1
27
53
35
60
8
6
10
10
Q30H4DB0Z
DB06
DB09
230/208-3
1
1
1
20
38
48
25
40
50
10
8
8
10
10
10
Q30H4DC0Z
DC06
DC09
460-3
1
1
1
10
19
24
15
25
25
14
12
10
14
12
10
Q36H4DA0Z
DA05
DA10
230/208-1
1
1
1 or 2
27
53
79
40
60
80
8
6
4
10
10
8
53
26
60
30
6
10
10
10
Q36H4DB0Z
DB06
DB09
DB15
230/208-3
1
1
1
1
22
40
49
52
25
45
50
60
10
8
8
6
10
10
10
10
Q36H4DC0Z
DC06
DC09
DC15
460-3
1
1
1
1
12
21
25
34
15
25
30
35
14
10
10
8
14
10
10
10
Содержание 11EER QH Series
Страница 16: ...Manual 2100 742A Page 16 of 54 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 18C If used ...
Страница 43: ...Manual 2100 742A Page 43 of 54 GRAPH 1 Q24H4 FAD Ventilation Delivery GRAPH 2 Q30H4 FAD Ventilation Delivery ...
Страница 44: ...Manual 2100 742A Page 44 of 54 GRAPH 3 Q36H4 FAD Ventilation Delivery ...