4.2 BUILDING-IN A FIRE IN GERMANY AND SWITZERLAND
Building-in the fi re against a wall in a casing/fi replace/chimney breast
False wall
is
mandatory
• A false wall is mandatory in the case of protective walls/walls with fl ammable
material. The recommended thickness of the false wall is at least 10 cm.
• The false wall must be of mineral construction, e.g. aerated concrete.
• The false wall must in turn be covered with minimal 10 cm of insulation (see table 1).
• The false wall must at least be built up to the place at which the chimney leaves the
convection area.
False wall
not
mandatory
• If the existing wall is at least 10 cm thick.
• If the existing wall does not contain fl ammable material.
• If the existing wall is not a bearing concrete or reinforced concrete wall and is at least
10 cm thick. In that case, a minimal 10 cm thick layer of insulation must be used and
the insulation must be closed tightly, and overlapping at the sides.
Содержание ENERGA 80-50
Страница 2: ......
Страница 3: ...3 ENERGA 80 50 ENERGA 80 50...
Страница 4: ...4 ENERGA 80 50...
Страница 6: ...6 ENERGA 80 50...
Страница 8: ...8 ENERGA 80 50...
Страница 10: ...10 ENERGA 80 50...
Страница 31: ...31 ENERGA 80 50 Dismantle the steel bottom plate Dismantle the lower air slider...
Страница 33: ...33 ENERGA 80 50 Dismantle the fan holder by unscrewing the screws and the fly nuts Fan holder plate rear...
Страница 41: ......
Страница 66: ...66 ENERGA 80 50 13 DIMENSIONS 13 1 ENERGA 80 50 Combustion air supply connection 125 mm...
Страница 67: ...67 ENERGA 80 50 13 1 1 ENERGA 80 50 3 sided 35 mm frame Combustion air supply connection 125 mm...
Страница 68: ...68 ENERGA 80 50 13 1 2 ENERGA 80 50 4 sided 35 mm frame Combustion air supply connection 125 mm...
Страница 74: ...74 ENERGA 80 50...
Страница 75: ......
Страница 76: ...01 011213 332127 Your Barbas dealer...