 Installation & Operations

Blü-Test Wireless Test Instruments

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 08/16/21

41521_BluTest_G2_ins

10 of 12

The Blü-Test unit is factory calibrated and comes with an NIST traceable certificate. The certificate is accessible 

via the Probe Settings screen.  You can tap the “View Calibration Certificate” button to view the certificate.  The 

Blü-Test should be re-calibrated once every year as a standard practice. The unit cannot be field calibrated and 

must be calibrated at the factory, which includes a thorough inspection, cleaning, calibration and an NIST traceable 

re-certification.

Sect. 13: Recalibration

Possible Problem: The probe will not link-up with the Bluetooth display device.

1. Be sure the display device has the Blü-Test App loaded and is Android OS 5.1 or Apple iOS 10 or higher.

2. Be sure the display device and the probe are turned on and close enough to each other (<30ft or 10m open air).

3. Cycle power to both the probe and the display device.

4. Verify that Bluetooth communication is turned on in your device.

Possible Problem: The temperature or humidity is not accurate.

1. Make sure the Blü-Test probe tip is near to the reference or field device.

2. Make sure that independent drafts are not affecting the reference or the Blü-Test probe.

3. Allow the Blü-Test probe to acclimate to the air before registering the reading. This may take between 2 to 5 minutes

Possible Problem: Probe will not go into logging mode.

1. Your onboard memory on the probe may be full.  To clear the memory, go to the probe settings screen via the 

dashboard.  Tap “Delete all logs from probe” button to erase log files from the probe.

Possible Problem: Log file is not downloading from the probe.

1. The log file may be very large so give it time to download. A week-long log file can take up to 30 minutes to 

download from the probe to the application. This is normal behavior.

Possible Problem: iOS smart device cannot mail csv files. 

1. Make sure the standard iOS mail application is enabled on your smart device.

Sect. 12: Diagnostics

TEMPERATURE ONLY UNITS:

The Blü-Test temperature only units can be cleaned with a damp cloth with an alcohol-

based disinfectant or mild soap. A double-ended brush is included to help with cleaning the 

seams on the body of the probe. Dry with a towel or warm blower after cleaning. The units 

should not be submerged or placed in a dishwasher. 

TEMPERATURE/HUMIDITY UNITS AND DIFFERENTIAL PRESSURE UNITS:

The Blü-Test temperature/humidity and differential pressure units can be cleaned with a 

damp cloth with an alcohol-based disinfectant or mild soap, but DO NOT get the tip of the 

temp/humidity probe wet in any way, and do not let liquid enter the ports of the differential 

pressure unit. A double-ended brush is included to help with cleaning the seams on the 

body the probe. Dry with a towel or warm blower after cleaning. The Blü-Test units should 

not be submerged or placed in a dishwasher. If liquid does infiltrate the probe tip of the 

temp/humidity unit, remove liquid immediately with a paper towel or cotton swab and dry 

with a warm blower. If grease infiltrates the probe, the unit may be damaged. Send it back 

to BAPI for service.
Note: The Piercing Temperature Probe is NSF certified and must be cleaned in a means that is acceptable to your local 

food inspector and/or regulatory compliance manager.

Sect. 10: Cleaning

Handle the unit with care because dropping or high vibrations could cause the battery to shake loose or the probe 

support to crack. The Blü-Test unit should be stored in a dry location with ambient temperatures between: 

<1 month: -20 to 50°C (-4 to 122°F) ● 1-3 months: -20 to 40°C (-4 to 104°F) ● 3-12 months: -20 to 20°C (-4 to 68°F)

Sect. 11: Storage

Fig. 34:

 Brush included 

for cleaning seams

Содержание Blu-Test

Страница 1: ...ows hands free measuring in ducts Reversible belt clip OLED displays measurements and cycles through other displays battery level log indicator etc Sealed probe tip can be used in liquids Gauge Graph...

Страница 2: ...10 11 Storage 10 12 Diagnostics 10 13 Recalibration Information 10 14 Specifications 11 Bl Test is a suite of handheld test instruments that communicate via Bluetooth 4 2 to the user s enabled Android...

Страница 3: ...ctivity no logging no active App present On Probe Log Storage Probe can store up to a million readings in a maximum of 31 log files Once the memory is full a new log file will automatically overwrite...

Страница 4: ...r download from the probe to the Bl Test application Tap the top left Download button to download the checked files to your device or tap the white down arrow to download individual files The down arr...

Страница 5: ...umidity log is selected as the primary log so the scale values on the axes only apply to that graph Sect 6 Application Logs Screen Overview Bl Test Application The Application Logs Screen different fr...

Страница 6: ...sites and locations screens along with exporting a comma separated values csv file of your sites and locations Fig 15 Sites Screen before adding sites Fig 16 Sites Screen with site added Fig 17 Locati...

Страница 7: ...ool will then provide the transmitter specifications including the accuracy at 8 and 16 mA accuracy at 25 50 and 75 of span linearity and power output shift The Tools Section of the Home Screen includ...

Страница 8: ...he application discovers Changes to specific probes can still be made via the gauges view of the specific probe Resistance to Temperature This tool will calculate the temperature when you enter the re...

Страница 9: ...Leave the probe in place for 2 minutes or until the reading stabilizes Outside air sensor measurement requires that the Bl Test probe be placed next to the outside air sensor This may require a ladde...

Страница 10: ...1 The log file may be very large so give it time to download A week long log file can take up to 30 minutes to download from the probe to the application This is normal behavior Possible Problem iOS...

Страница 11: ...sure Probes Low Range 0 25 of FS Span 1 to 1 WC 250 to 250 Pa at 77 F 25 C Standard Range 0 25 of FS Span 5 to 5 WC 1 250 to 1 250 Pa at 77 F 25 C Burst Pressure Differential Pressure Probes Low Range...

Страница 12: ...735 4800 Fax 1 608 735 4804 E mail sales bapihvac com Web www bapihvac com Google Play and the Google Play logo are trademarks of Google LLC Apple and the Apple logo are trademarks of Apple Inc regis...

Отзывы: