Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 04/23/18
41012_ins_quantum_slider_temp_display
4 of 6
BAPI-Stat Quantum sensor comes with a display, slider setpoint adjustment and optional override.
Temperature:
Displayed in Fahrenheit or Celsius in the major display. (Field adjustable via the “F/C” switch on DIP Switch SW5.)
Temperature Setpoint Slider:
Moving the slidepot enough to change the setpoint will display the setpoint in the major of the display. The setpoint
temperature display will flash the digits indicating that setpoint is being changed.
Override Button:
When the override button is pressed on display units, the BAPI-Man Icon will display (Fig
8). A dry resistance of less than 15 ohms appears across the override output.
Note:
The unit must receive a confirmation (ground) signal on the “OCCUPY” terminal for
the BAPI-Man to remain visible on the screen. Pressing the Override button will light the
BAPI-Man icon; however, if no confirmation signal is received, then the BAPI-Man will go
blank (disappear) after 5 seconds.
Upon receiving a first confirmation (ground) signal on the “OCCUPY” terminal, the
BAPI-Man will show occupied (Solid). The BAPI-Man will then show unoccupied (Hollow)
whenever the confirmation signal is removed and occupied when the signal is returned.
The only way to blank the BAPI-Man from the display after it has received a first
confirmation signal is to cycle power.
Front Panel & Control Descriptions
Fig. 7:
BAPI-Stat “Quantum” with
Display, Slider Setpoint and Override.
BAPI-Man Icon
Major Display
Hollow
equals
“Unoccupied”
Fig. 8:
BAPI-Man Icon
Solid
equals
“Occupied”
Temperature
Setpoint Slider
Override
Button