Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 04/23/18
41012_ins_quantum_slider_temp_display
3 of 6
Optional Test and Balance Switch (SW7)
Optional Communication Jack Wiring
Fig. 5:
C35L Comm. Jack
(3.5mm plug shown for
clarity)
Fig. 6:
C11/C22
Comm. Jack
PIN #
WIRE COLOR
1
Not Connected
2
Black
3
Red
4
Yellow
5
Green
6
Not Connected
C11L/C22L Comm. Jack Wiring
Location
WIRE COLOR
Ground
Black
Tip
White
Ring
Red
C35L Comm. Jack Wiring
Sensor Type
Low Temp (40° F)
Resistance Value
High Temp (105°F)
Resistance Value
1000Ω RTD
1.02KΩ (41.20°F)
1.15KΩ (101.5°F)
3000Ω Thermistor
7.87KΩ (39.8°F)
1.5KΩ (106.8°F)
10K-2 Thermistor
30.1KΩ (34.9°F)
4.75Ω (109.1°F)
10K-3 Thermistor
26.7KΩ (35.9°F)
5.11KΩ (108.4°F)
10K-3(11K) Thermistor
7.32KΩ (43.7°F)
3.65Ω (105.2°F)
Test and Balance Switch (SW7)
NORM: Sensor operates normally
LOW: Sets the sensor value low
HIGH: Sets the sensor value high
On the Test and Balance Switch (SW7), the NORM position allows the
real sensor to be monitored. The HIGH position forces the output to a
very hot reading and the LOW position forces a very cold reading (see
Table below).
Fig. 4:
Back Plate
Comm. Jack
Locations