background image

Installation & Operating Instructions

BAPI-Stat “Quantum” Temperature Sensor with Display 

and Slider Setpoint

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 04/23/18

41012_ins_quantum_slider_temp_display

3 of 6

Optional Test and Balance Switch (SW7)

Optional Communication Jack Wiring

Fig. 5: 

C35L Comm. Jack

(3.5mm plug shown for 

clarity)

Fig. 6:

C11/C22

Comm. Jack

PIN #

WIRE COLOR

1

Not Connected

2

Black

3

Red

4

Yellow

5

Green

6

Not Connected

C11L/C22L Comm. Jack Wiring

Location

WIRE COLOR

Ground

Black

Tip

White

Ring

Red

C35L Comm. Jack Wiring

Sensor Type

Low Temp (40° F)

Resistance Value

High Temp (105°F)

Resistance Value

1000Ω RTD

1.02KΩ (41.20°F)

1.15KΩ (101.5°F)

3000Ω Thermistor

7.87KΩ (39.8°F)

1.5KΩ (106.8°F)

10K-2 Thermistor

30.1KΩ (34.9°F)

4.75Ω (109.1°F)

10K-3 Thermistor

26.7KΩ (35.9°F)

5.11KΩ (108.4°F)

10K-3(11K) Thermistor

7.32KΩ (43.7°F)

3.65Ω (105.2°F)

Test and Balance Switch (SW7)

NORM: Sensor operates normally

LOW: Sets the sensor value low

HIGH: Sets the sensor value high

On the Test and Balance Switch (SW7), the NORM position allows the 

real sensor to be monitored. The HIGH position forces the output to a 

very hot reading and the LOW position forces a very cold reading (see 

Table below).

Fig. 4: 

Back Plate 

Comm. Jack 

Locations