Installation & Operating Instructions

BAPI-Stat “Quantum” Temperature Sensor with Display 

and Slider Setpoint

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 04/23/18

41012_ins_quantum_slider_temp_display

2 of 6

Termination

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger 

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. 

Do NOT run this device’s wiring in the same conduit as AC power wiring.  BAPI’s tests show fluctuating and inaccurate 

signals are possible when AC power wiring is in the same conduit as the signal lines.  If you are experiencing any of these 

difficulties, please contact your BAPI representative

.

Fig. 3:

 BAPI-Stat “Quantum” 

Circuit Board

BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and void the warranty.

TERMINAL 

DESCRIPTION

GND ........................... Power Supply Ground (Common to the controller)
V+ .............................. Power Supply Hot (See specs for voltage details) 
W1 ............................. Not Used
OCCUPY ................... BAPI-Man Occ/Un-Occ indicator Input. 

Ground terminal to fill in the BAPI-Man icon for 

Occupied.

SEN1 & SEN2 ........... Sensor output per order (resistive). No polarity.   

*If the unit is a common ground configuration, see 

“Grounding Note” below.  

SET1 & SET2 

A)   Setpoint output per order (resistive). *If the 

unit is a common ground configuration, see 

“Grounding Note” below.

 

B)   Setpoint output per order (voltage). SET1 is 

“+”, SET2 is “-”. 

OVR1 & OVR2........... Override Output (Dry contact) if unit is ordered 

with Override as a Separate Output (-J). The 

override can also be ordered as a momentary 

shunt across the sensor terminals SEN1 & SEN2 

(-N) or as a momentary shunt across the setpoint 

terminals SET1 & SET2 (-P).  *If the unit is a 

common ground configuration, see “Grounding 

Note” below. 

EXT-TEMP & EXT-GND .. Remote sensor terminals.  No polarity.  *If the 

unit is a common ground configuration, see 

“Grounding Note” below. To use these terminals, 

a 10K-2 thermistor sensor must be ordered 

separately and the temperature value from this 

sensor will be displayed on the LCD but will not 

be sent to the controller. Max wire distance for the 

external sensor is 25 feet. 

*Grounding Note:

 

Common Ground or Differential Ground configurations are selected per order (Common Ground is default).  The 

Differential Ground configuration indicates that SEN2, SET2, OVR2 and EXT-GND must all be wired separately (No 

internal common connection).  The Common Ground configuration indicates that SEN2, SET2, OVR2 and EXT-GND are 

connected to GND internally (All internally common).