Installation & Operating Instructions

BAPI-Stat “Quantum” Temperature Sensor with Display 

and Slider Setpoint

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 04/23/18

41012_ins_quantum_slider_temp_display

1 of 6

Product Identification and Overview

Fig. 1:

  BAPI-Stat 

“Quantum” with slider 

setpoint adjustment, 

override button and 

provided screw pack.

The BAPI-Stat “Quantum” style room temperature sensor features a 

large format LCD and slider setpoint adjustment. Additional options 

include button override and communication jack.
The setpoint is available as a resistance or voltage output. The 

override is a momentary closure signal that can be configured in 

parallel with the sensor or setpoint, or as a separate momentary 

output. 

Mounting

JUNCTION BOX

1.   Pull the wire through the wall and out of the junction box, leaving about 6 

inches free.

2.   Pull the wire through the hole in the base plate.
3.   Secure the base to the box using the #6-32 x 1/2 inch mounting screw 

provided.

4.   Terminate the unit according to the guidelines in the 

Termination 

section.

5.   Attach Cover by latching it to the top of the base, rotating the cover down 

and snapping it into place.

6.   Secure the cover by backing out the lock-down screws using a 1/16” Allen 

wrench until they are flush with the bottom of the cover.

DRYWALL MOUNTING

1.   Place the base plate against the wall where you want to mount the sensor.
2.   Using a pencil, mark out the two mounting holes and the area where the 

wires will come through the wall.

3.   Drill two 3/16” holes in the center of each marked mounting hole. Insert a 

drywall anchor into each hole.

4.  Drill one 1/2” hole in the middle of the marked wiring area.
5.   Pull the wire through the wall and out the 1/2” hole, leaving about 6” free.
6.   Pull the wire through the hole in the base plate.
7.   Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8.   Terminate the unit according to the guidelines in the 

Termination 

section.

9.   Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover 

by backing out the lock-down screws using a 1/16” Allen wrench until they are flush with the bottom of the cover.

NOTE: 

In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous 

readings, condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with 

insulation in the junction box.

Fig. 2:

 Mounting hardware is provided 

for both J-Box and drywall installation 

(J-Box installation shown)