Installation & Operating Instructions
BAPI-Stat “Quantum” Temperature Sensor with Display
and Slider Setpoint
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 04/23/18
41012_ins_quantum_slider_temp_display
5 of 6
Optional Technician Adjustments
The unit is shipped ready to install. The following Setup or Program Menu Changes are available if the installer decides to
change the factory settings.
ENTERING PROGRAM MODE TO ADJUST PARAMETERS
(see Figs 9-11 for adjustment tools)
1. Power unit and set DIP Switch SW5 #2 (PROG) to ON (right). The LCD will show a page number
(P1-P9). P1-P9 will flash to indicate that display parameter can be adjusted.
2. Slide Potentiometer J1 is used to scroll up and down through pages and adjusting the page
parameters.
NOTE: For units with Temperature Setpoint, the Slide Potentiometer will extend outside the
enclosure. For units without Temperature Setpoint, the Slide Potentiometer will not be extended outside the enclosure.
3. Push Switch SW8 as “Enter” to switch between page number and adjusting the page parameter.
4. After a page parameter has been adjusted, push Switch SW8 to confirm the change.
5. To exit Program Mode, Set DIP Switch SW5 #2 (PROG) to OFF (left).
Note: DIP Switch SW5 #1 (°F/C) can be used to switch the display between °F and °C.
Parameter
Page
Temperature Offset
P1
Item
Display Action
0
Setpoint Enabled
1
Setpoint Disabled (pushbutton only): Display shows
setpoint when activated, but can't be changed
2
Setpoint Display Only: Shows setpoint only, does not
display local temperature
3
Setpoint Not Displayed: Setpoint can be changed, but
will not display
Item
Display Action
0
Display in whole digits
1
Display in 0.5° increments, °F and °C
2
Display in 0.1° increments, °F and °C
Temperature Setpoint
Display Low
P4
Temperature Setpoint
Display High
P5
Temperature Setpoint
Output Low
P6
Temperature Setpoint
Output High
P7
Temperature Setpoint
Value
P8
User Fan/Mode Setpoint
P9
Programming Pages
±5° in 0.1° increments
Adjustment
Adjust the Low Temperature of the setpoint range
Shows Fan/Mode setpoint on units configured with Mode/
Setpoint (Ready Only. Pushbutton only. Major display shows 0)
Shows High Setpoint Output
(Read Only. Displayed in 10 ohm resolution)
P2
P3
Temperature Display
Setpoint Lockout
Adjust the High Temperature of the setpoint range
Shows Low Setpoint Output
(Read Only. Displayed in 10 ohm resolution)
Shows temperature setpoint value (Ready Only)
Fig. 10:
J1 Slide
Potentiometer
Fig. 11:
Enter
Switch SW8
Fig. 9:
DIP
Switch SW5