Optional Technician Adjustments

The unit is shipped ready to install. The following Setup or Program Menu Changes are available if the installer decides to 

change the factory settings. 

ENTERING PROGRAM MODE TO ADJUST PARAMETERS 

(see Figs 9-11 for adjustment tools)

1.  Power unit and set DIP Switch SW5 #2 (PROG) to ON (right). The LCD will show a page number 

(P1-P9). P1-P9 will flash to indicate that display parameter can be adjusted.

2.  Slide Potentiometer J1 is used to scroll up and down through pages and adjusting the page 

parameters.
NOTE: For units with Temperature Setpoint, the Slide Potentiometer will extend outside the 

enclosure. For units without Temperature Setpoint, the Slide Potentiometer will not be extended outside the enclosure.

3.  Push Switch SW8 as “Enter” to switch between page number and adjusting the page parameter.
4.  After a page parameter has been adjusted, push Switch SW8 to confirm the change.
5.  To exit Program Mode, Set DIP Switch SW5 #2 (PROG) to OFF (left).
  Note: DIP Switch SW5 #1 (°F/C) can be used to switch the display between °F and °C.

Parameter

Page

Temperature Offset

P1

Item

Display Action

0

Setpoint Enabled

1

Setpoint Disabled (pushbutton only): Display shows 

setpoint when activated, but can't be changed

2

Setpoint Display Only: Shows setpoint only, does not 

display local temperature

3

Setpoint Not Displayed: Setpoint can be changed, but 

will not display

Item

Display Action

0

Display in whole digits

1

Display in 0.5° increments, °F and °C

2

Display in 0.1° increments, °F and °C

Temperature Setpoint 

Display Low

P4

Temperature Setpoint 

Display High

P5

Temperature Setpoint 

Output Low

P6

Temperature Setpoint 

Output High

P7

Temperature Setpoint 

Value

P8

User Fan/Mode Setpoint

P9

Programming Pages

±5° in 0.1° increments

Adjustment

Adjust the Low Temperature of the setpoint range

Shows Fan/Mode setpoint on units configured with Mode/

Setpoint (Ready Only. Pushbutton only. Major display shows 0)

Shows High Setpoint Output

(Read Only. Displayed in 10 ohm resolution)

P2

P3

Temperature Display

Setpoint Lockout

Adjust the High Temperature of the setpoint range

Shows Low Setpoint Output

(Read Only. Displayed in 10 ohm resolution)

Shows temperature setpoint value (Ready Only)