Response and Recovery Times
Input to Output Response Time (Input Stop to Output Off): see the
Configuration Summary in the Software, as it can vary
Input Recovery Time (Stop to Run): 250 ms typical, 400 ms maximum
Virtual Input (Mute Enable and On/Off) Timing: RPI + 200 ms typical
Virtual Input (Manual Reset and Cancel Delay) Timing: see
Safety Input Devices (XS/SC26-2 FID 2 Only and SC10-2)
on page 44
for details
Delay Tolerance
±(0.02% + 2 scan times)
Safety Outputs
3 NO sets of contacts for each output channel (RO1 and RO2). Each
normally open output is a series connection of contacts from two
forced-guided (mechanically linked) relays. RO1 consists of relays K1
and K2. RO2 consists of relays K3 and K4.
Operating Conditions
Temperature: 0 °C to +55 °C (+32 °F to +131 °F) (see Temperature
Derating graph)
Storage Temperature: –30 °C to +65 °C (–22 °F to +149 °F)
Humidity: 90% at +50 °C maximum relative humidity (non-condensing)
Operating Altitude: 2000 m maximum (6562 ft maximum)
Environmental Rating
NEMA 1 (IEC IP20), for use inside NEMA 3 (IEC IP54) or better
enclosure
Mechanical Stress
Shock: 15 g for 11 ms, half sine, 18 shocks total (per IEC 61131-2)
Vibration: 3.5 mm occasional / 1.75 mm continuous at 5 Hz to 9 Hz, 1.0
g occasional and 0.5 g continuous at 9 Hz to 150 Hz: all at 10 sweep
cycles per axis (per IEC 61131-2)
Contacts
AgNi + 0.2 μm gold
Overvoltage Category
Output relay contact voltage of 1 V to 150 V ac/dc: Category III Output
relay contact voltage of 151 V to 250 V ac/dc: Category II (Category III,
if appropriate overvoltage reduction is provided, as described in this
document.)
Individual Contact Current Rating
Refer to the Temperature Derating graph when more than one contact
output is used.
Minimum
Maximum
Voltage
10 V ac/dc
250 V ac / 24 V dc
Current
10 mA ac/dc
6 A
Power
100 mW (100 mVA)
200 W (2000 VA)
Switching Capacity (IEC 60947-5-1)
AC 15
NO: 250 V ac, 3 A
DC 13
NO: 24 V dc, 2 A
DC 13 at 0.1 Hz
NO: 24 V dc, 4 A
Mechanical Life
20,000,000 cycles
Electrical Life
50,000 cycles at full resistive load
UL Pilot Duty
B300 Q300
B10d Values
Voltage
Current
B10d
230 V ac
2 A
350,000
230 V ac
1 A
1,000,000
24 V dc
≤ 4 A
10,000,000
Push-in Spring Clamp Terminals
Important: Clamp terminals are designed for
one wire only. If more than one wire is
connected to a terminal, a wire could loosen
or become completely disconnected from the
terminal, causing a short.
Use a stranded wire or a wire with an
accompanying ferrule. Tinned wires are not
recommended.
After inserting the wire into the terminal, tug
the wire to make sure it is properly retained. If
the wire is not retained, consider using a
different wiring solution.
Wire Size: 24 to 14 AWG, 0.2 mm² to 2.08 mm²
XS/SC26-2 and SC10-2 Safety Controllers