background image

MSC..-1S..E 

Supplement: MINI-SCREEN Models with Selectable Trip/Latch Output

 

 

P/N 68980     

 

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

Before the reset of the safeguard is performed, safe work procedures must ensure that a 

start-up procedure is followed and that the operator verifies that the entire hazardous area is 

clear of all personnel. If any areas can not be observed from the switch location, additional 

supplemental safeguarding must be used to guard those areas. At a minimum, this should 

consist of visual and audible warnings of machine start-up.
A reset switch that is key-actuated can give some level of personal or supervisory control by 

removing the key and taking it into the guarded area. This will hinder a reset while the key is 

under the control of one individual. However, this method must not be relied upon solely to 

guard against unintended or inadvertent reset, because others may enter the safeguarded 

area unnoticed, or additional keys may be in the possession of others.

Section 3. Addition

3.(s) Controller Module Configuration

Replace all references in Section 3.4 and Figure 18 of “Auto Power-up” with “Trip/Latch 

Output Select.”
Replace the sub-paragraph titled “Auto Power-up Feature ON or OFF” with the following:

Trip/Latch Output Select (Auto/Manual Reset)

Locate the DIP switches to configure the receiver for Trip Output (Auto Reset) or Latch Output 

(Manual Reset) as described by Figure 18. If Trip Output is selected, the FSD/SSD outputs 

will turn ON as soon as power is applied, the unit passes an internal self-test/synchronization, 

and recognizes that all beams are clear. The Trip Output will also automatically reset after 

all interruptions of one or more beam(s) have been cleared. If Latch Output is selected, the 

MINI-SCREEN requires a monitored manual reset at power-up and each time all interruptions 

of one or more beam(s) have been cleared. Switch #2 must be set identically at both banks A 

and B.
Regardless of the setting of this switch, a key reset is always necessary to recover from an 

internal lockout condition.
See Sections 2.2(s), 2.10(s), and 3.2.1.1(s) for Warnings and further information.

Section 3..2 Replacement

3..2(s) External Device Monitoring and System Power

Temporary Connection

For the initial checkout procedure, the External Device Monitoring (EDM) must be temporarily 

configured for “No Monitoring” (jumper TB2 Mon a and Mon b); refer to Figure 20(s) and 

Section 2.8(s). This will allow the MINI-SCREEN System to be checked out as a stand-alone 

system, before permanent connections are made to the guarded machine.
Verify that the power has been removed from the machine or that power is not available to 

the machine controls or actuators. Also verify that the machine controls (MPCEs) are not 

connected to the FSD and SSD outputs at this time. Permanent connections will be made 

after MINI-SCREEN initial checkout; see Section 3.5.5(s).
Connection of System AC power (e.g. 115V ac) is at the L and the N terminals of control box 

wiring barrier TB1. All wiring must comply with NEC and local wiring codes. Do not operate 

the MINI-SCREEN System without a proper earth ground connection at either of the PE/GND 

symbols.

 WARNING . . . 

Use of 

MINI-SCREEN Systems for 

Perimeter Guarding

If a MINI-SCREEN System is installed for 
perimeter guarding, the system MUST 
require actuation of a Reset switch before 
initiating the dangerous machine motion 
following an interruption of the defined 
area.
If a MINI-SCREEN System is used for 
perimeter guarding,
 the Machine Primary 
Control Elements (MPCEs) of the guarded 
machine must be wired so that the FSD 
outputs of the control box cause a latched 
response of the MPCEs. The MPCEs must 
be reset only by actuation of a Reset switch.
The Reset switch must be located outside 
of, and not be accessible from within, the 
area of dangerous motion, and it must be 
positioned so that the area of dangerous 
motion may be observed by the switch 
operator during the reset operation.
Additional safeguarding, as described by 
the ANSI B11 series of safety requirements 
or other appropriate standards, must be 
used if any space between either defined 
area and any danger point is large enough 
to allow a person to stand undetected by the 
MINI-SCREEN System. Failure to observe 
this warning could result in serious bodily 
injury or death.

Содержание MSC 1S Series

Страница 1: ...o include Trip Latch output select switches and the addition of a one channel External Device Monitoring EDM input The primary instruction manual for these control boxes is Banner p n 39022 The inform...

Страница 2: ...nstruction manual and Section 3 4 s in this supplement Trip Output Upon power up when the control box is configured for Trip Output the FSD and SSD outputs will automatically close once power is appli...

Страница 3: ...ust be jumpered if EDM is not used If the MINI SCREEN is set for No Monitoring the user must ensure that any single failure of the external devices will not result in a hazardous condition and will pr...

Страница 4: ...ust be eliminated or reduced to acceptable levels as determined by the user by employing supplemental safeguarding One solution is to combine perimeter guarding with area guarding so that an individua...

Страница 5: ...internal lockout condition See Sections 2 2 s 2 10 s and 3 2 1 1 s for Warnings and further information Section 3 5 2 Replacement 3 5 2 s External Device Monitoring and System Power Temporary Connecti...

Страница 6: ...ght NOTE See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23a s Generic Machine Interface MINI SCREEN MSC 1S2E Systems with the MSA RM 1 relay...

Страница 7: ...Circuit See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23b s Generic MaAchine Interface MINI SCREEN MSC 1T3E Systems with the MSA RM 2 relay...

Страница 8: ...eplacement 3 5 6 s Auxiliary Relay Output The MSC 1S E controller has an Auxiliary Monitor Relay output See Figure 5 in the primary manual for operating status condition and output status The action o...

Страница 9: ...ossible to reset the MINI SCREEN in this condition If the measurement is approximately 0V dc there is likely a closed circuit The problem is likely a slow or sticky MPCE causing the EDM input to close...

Страница 10: ...ent Status LEDs Diagnostic Indicator LEDs Controller Module Assembly Red Intermittently flashing 4 red LED indicates presence of optical or electrical noise Green LED indicator is always ON except whe...

Страница 11: ...e contacts of the monitored device must be capable of switching 15 to 50V dc at 20 to 100 mA Output Configuration FSD1 FSD2 and SSD Replaces Output Configuration category Relays have forced guided con...

Страница 12: ...Banner Engineering Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective a...

Отзывы: