background image

MSC..-1S..E 

Supplement: MINI-SCREEN Models with Selectable Trip/Latch Output

     

P/N 68980

 

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

Section 2.10 Addition

2.10(s) External Key Reset

If it is not possible to mount the control box so that it complies with the warning at right, an 

external Reset switch must be provided for the installation that can comply with the warning. 

The user must supply a means to reset the MINI-SCREEN system if a latch condition occurs 

(after clearing an interruption of the defined area in Latch mode), or after a lockout condition 

(see Section 5 of the primary instruction manual).
When wiring external switches, the corresponding control box-mounted key reset switches 

should be disconnected (or if that is not possible, the keys removed and placed under 

supervisory control). The key reset (manual reset) connection is located at TB2 “Key 1” and 

“Key 2” (see Figure 20 in the primary manual). If disconnected, loose wires from the Key 

Reset switches must be secured (i.e., tape or wire-tie the loose ends) so they do not cause 

shorts within the control box.
All reset switches must be located outside the guarded area, where the switch operator has 

a full and unobstructed view of the entire guarded area and any associated hazards while the 

reset is performed. The reset switch also must not be reachable from within the guarded area 

and must be protected (through the use of rings, or guards, for example) against unauthorized 

or inadvertent operation.
The reset switch must be a normally open switch that is held closed for approximately 0.5 

seconds, and then re-opened to accomplish the reset. In the associated primary instruction 

manual, the “RUN” position is the open condition of the switch; the “Reset” position is closed. 

The switch must be capable of switching 15 to 50V dc at 20 to 100 mA.

Section 3.2.1 Addition

3.2.1.1(s) Pass-Through Hazards

Methods of Reducing or Eliminating Pass-Through Hazards

The pass-through hazard must be eliminated or reduced to acceptable levels (as determined 

by the user) by employing supplemental safeguarding. One solution is to combine perimeter 

guarding with area guarding so that an individual is continually sensed while within the 

hazardous area. Supplemental safeguards for area guarding include safety mats, area 

scanners, and horizontally mounted safety light curtains. 
It is also possible to reduce the separation distance by reducing the stopping time of the 

machine, or by using a full-length safety light curtain with a small object detection capability 

that reduces the Dpf adder. While it is recommended to eliminate the pass-through hazard 

altogether, this may not be a viable option due to cell or machine layout, machine capabilities, 

cost constraints, environmental, or other application considerations.
An alternate method is to ensure that once the safeguarding device is tripped, resulting in 

stopping or removing the hazard, the safeguard will latch in a tripped condition, thus requiring 

a deliberate manual action to reset the safeguard. This type of supplemental safeguarding 

relies upon the location of the reset switch or actuating control as well as safe work 

procedures to prevent unexpected start or restart. 
The location of the reset switch or actuating control must be located outside the guarded 

area, and provide the switch operator with a full unobstructed view of the entire guarded area 

and any associated hazards as the reset is preformed. The reset switch or actuating control 

must also be positioned so it cannot be reached from within the guarded area and must be 

protected against unintended or inadvertent operation (e.g., rings or guards).

WARNING . . . 

Reset 

Switch Location

Reset switch(es) must be accessible 
only from outside, and in full view of, 
the hazardous area. Reset switches 
must also be out of reach from within 
the safeguarded area, and must be 
protected against unauthorized or 
inadvertent operation (e.g., through the 
use of rings or guards)
. If any areas are 
not visible from the Reset switch, additional 
means of safeguarding must be provided as 
described by the ANSI B11 series of safety 
requirements or other appropriate standards.

Содержание MSC 1S Series

Страница 1: ...o include Trip Latch output select switches and the addition of a one channel External Device Monitoring EDM input The primary instruction manual for these control boxes is Banner p n 39022 The inform...

Страница 2: ...nstruction manual and Section 3 4 s in this supplement Trip Output Upon power up when the control box is configured for Trip Output the FSD and SSD outputs will automatically close once power is appli...

Страница 3: ...ust be jumpered if EDM is not used If the MINI SCREEN is set for No Monitoring the user must ensure that any single failure of the external devices will not result in a hazardous condition and will pr...

Страница 4: ...ust be eliminated or reduced to acceptable levels as determined by the user by employing supplemental safeguarding One solution is to combine perimeter guarding with area guarding so that an individua...

Страница 5: ...internal lockout condition See Sections 2 2 s 2 10 s and 3 2 1 1 s for Warnings and further information Section 3 5 2 Replacement 3 5 2 s External Device Monitoring and System Power Temporary Connecti...

Страница 6: ...ght NOTE See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23a s Generic Machine Interface MINI SCREEN MSC 1S2E Systems with the MSA RM 1 relay...

Страница 7: ...Circuit See Sections 2 10 s and 3 2 1 1 s on the installation of the Key Reset switch Figure 23 Replacement Figure 23b s Generic MaAchine Interface MINI SCREEN MSC 1T3E Systems with the MSA RM 2 relay...

Страница 8: ...eplacement 3 5 6 s Auxiliary Relay Output The MSC 1S E controller has an Auxiliary Monitor Relay output See Figure 5 in the primary manual for operating status condition and output status The action o...

Страница 9: ...ossible to reset the MINI SCREEN in this condition If the measurement is approximately 0V dc there is likely a closed circuit The problem is likely a slow or sticky MPCE causing the EDM input to close...

Страница 10: ...ent Status LEDs Diagnostic Indicator LEDs Controller Module Assembly Red Intermittently flashing 4 red LED indicates presence of optical or electrical noise Green LED indicator is always ON except whe...

Страница 11: ...e contacts of the monitored device must be capable of switching 15 to 50V dc at 20 to 100 mA Output Configuration FSD1 FSD2 and SSD Replaces Output Configuration category Relays have forced guided con...

Страница 12: ...Banner Engineering Corp warrants its products to be free from defects for one year Banner Engineering Corp will repair or replace free of charge any product of its manufacture found to be defective a...

Отзывы: