F4 PLUS
13
UK
FINAL CHECKS AND TESTING
POWER THE DEVICES
Before powering the control unit, check the following:
1) Check that the dip switches and trimmers have been set properly according to requirements.
2) Check the electrical connections; Improper connection may cause damage to the control unit and the operator.
3) Check that the red LEDs of the safety devices are on and the yellow LEDs off
4) Check that when engaging any limit switches used the corresponding LEDs come on.
5) Check that when passing through the beam of the photocells the corresponding LED goes off.
6) Check that the motors are locked and ready for operation. Remove any obstacles from the operating range of the
gate, then give the START command. Upon the first command, the control unit starts an opening phase; check that
the motor rotation direction is correct.
6) If not, invert the wires of terminals 1-3 and/or 4-6.
7) Fine adjust the trimmers.
Trimmer V1 adjusted to maximum.
Trimmers V2, V3 and V4 adjusted to half their travel.
DEFAULT SETTINGS
TRIMMER ADJUSTMENT
V1
FORCE
FUNCTION
DESCRIPTION
TRIMMER
V2
V4
V3
Turned clockwise it adjusts the motor torque from 40% to 98%.
For the first 3 seconds pickup occurs.
Turned clockwise it adjusts the PAUSE TIME from 2 to 100 seconds. Adjusted
to minimum, it disables the pause time = STEP-BY-STEP function.
Turned clockwise, it adjusts the delay time between the start of the closing
mouvement of motor 2 and the start of the closing of motor 1 (from 0 to 20
seconds). The phase shift during opening is fixed at 2 seconds. With V3 set to
minimum the delays are cancelled both during opening and closing
double sliding gate version) and the WATER HAMMER function is disabled.
Turned clockwise, it adjusts the RUN TIME from 2 to 100 seconds.
PHASE SHIFT
TIME
RUN TIME
PAUSE TIME
There are 4 trimmers (V1-V2-V3-V4) on the F4PLUS control unit to adjust the following:
DEFAULT SETTINGS (DIP SWITCH)
DIP SWITCHES 1, 2, 3, 9, 10 OFF; DIP SWITCHES 4, 5, 6, 7, 8 ON