Before any installation or maintenance operation, ensure that the power supply has been disconnected.!!

FAULT

POSSIBLE CAUSES and SOLUTIONS

Red 24 Vac LED off

Yellow LEDs always on

The transmitter has a

small range

The card does not learn

the TX code

After the run time the gate

does not reclose

The gate does not perform a

phase shift when it starts

The operator does not

open or reclose

The flashlight is on but the

gate does not move.

Red LEDs

FA1-FC1-FA2-FC2-

PHOTOCELL off

After the motors have stopped,

the flashlight connected to

terminals 7-8 does not go off.

Red STOP LED off

Check the 230 Vac power supply and the relevant fuse F1(5A)

Check that the START and PEDESTRIAN GATE inputs have been connected

to NO buttons.

Check that DIP9 is set to ON. If only 2 limit switches are used, the relevant

DIP SWITCHES must set to OFF, the other 2 to ON.

Check that the trimmer V4 (Pause) is not turned completely anticlockwise.

Check that the trimmer V3 (closing delay) is not turned completely anticlockwise.

Check that the red LEDs are on (except the LED of the limit switch active at

that moment) and the yellow ones off.
Start has been pressed with the photocells engaged. Check that the photocells

are not engaged; once released the gate will start moving.

Check that the relevant inputs and safety switches are connected

(FA1-FC1-FA2-FC2-PHOTOCELL) or the relevant DIP SWITCH set to ON.

Check the fuse F2 (0.16A).
Check that the STOP input is connected to an NC button or that a jumper has been

connected between the terminals 23 and 25 (WARNING: the STOP intervention

causes a functional stop and NOT a safety stop).

Check the maximum number of codes that can be stored (200).  Check if remote

controls of the same family as the first are being learned: DIP SWITCH or ROLLING.

Check that the frequency of the radio control is the same as the receiver.

Check that the antenna has been positioned properly (braid terminal 26, core terminal

27,if a built-in radio or AU01630N receiver is used) (if an AU01710 plug-in receiver is

used, the antenna must be connected to the terminals on the receiver).

Check that there are no sources of disturbances in the vicinity which limit the range.

TROUBLESHOOTING

Upon  starting  the  gate 

does not execute the water 

hammer.

Check that DIP3 is set to ON and check  that TRIMMER V3 is not on 0.

Содержание GBD AS04180

Страница 1: ...F4 PLUS I UK F E D P NL GR F4 PLUS AS04180 Apparecchiatura elettronica ISTRUZIONI PER L INSTALLAZIONE Electronic control unit INSTRUCTIONS FOR INSTALLATIONS...

Страница 2: ...alasnormasvigentes La empresa Gi Bi Di S r l se reserva el derecho de modificar los datos t cnicos sin previo aviso en funci ndelaevoluci ndelproducto POR FAVOR LEER CON ATENCI N ESTE MANUAL ANTES DE...

Страница 3: ...n Start fussganger funktion Start peatonal Start pass peones Start voetgangers Start 230Vac 40W MAX 1 2 3 4 5 6 7 8 M2 MOTOR CLOSE LAMP LAMP MOTOR OPEN MOTOR CLOSE MOTOR COM MOTOR OPEN MOTOR COM M1 EA...

Страница 4: ...he control LEDs red for the safety switches NC contacts yellow for the controls NA contacts the extractable terminal boards and the silk screen printing on the printed circuit indicating connections a...

Страница 5: ...r improper use of the product may compromise system safety Keep all the materials contained in the packaging away from children since they pose a potential risk The manufacturer declines all responsib...

Страница 6: ...PHOTOCELLS and ACCESSORIES max 8W 2 pair of photocells radio receiver STOP input NC if not used connect with jumper to terminal 25 Input for PEDESTRIAN GATE START NA acts on motor 1 COMMON input for S...

Страница 7: ...tive for 3 minutes after the run time max 100W In this mode the terminals 28 29 can be used to connect a flashlight without flashing circuit code 70107 Enables the STEP BY STEP functions one START com...

Страница 8: ...TrimmerV1adjustedtomaximum TrimmersV2 V3andV4adjustedtohalftheirtravel DEFAULT SETTINGS TRIMMER ADJUSTMENT V1 FORCE FUNCTION DESCRIPTION TRIMMER V2 V4 V3 Turned clockwise it adjusts the motor torque...

Страница 9: ...the limit switch active at that moment and the yellow ones off Start has been pressed with the photocells engaged Check that the photocells are not engaged once released the gate will start moving Ch...

Страница 10: ...the products ELECTRONIC CONTROL UNIT F4 PLUS are in conformity with the following CEE Directives EMC Directive 2004 108 CE and subsequent amendments and that the following harmonised standards have be...

Страница 11: ...DI S r l 46025 Poggio Rusco MN ITALY Tel 39 0386 52 20 11 Fax 39 0386 52 20 31 E mail comm gibidi com Numero Verde 800 290156 Via Abetone Brennero 177 B w w w g i b i d i c o m Cod AIC1071 07 2008 Re...

Отзывы: