STARTING UP AND REGULATION WITH LIGHT OIL

1)  Check that the characteristics of the nozzle (delivery and 

spray angle) are suitable for the furnace (see BT 9353/1). 

 

If not, replace it.

2)  Check that there is fuel in the cistern and that it is, at least 

visually; suitable for the burner.

3) 

Check that there is water in the boiler and that the system’s gate 

valves are open.

4)  Check, with absolute certainty, that the discharge of combustion 

products can take place freely (boiler and chimney lock-gates 

should be open).

5)  Make sure that the voltage of the electric line to which the bur

-

ner is to be connected, corresponds to that requested by the 

manufacturer, and that the motor’s electrical connections have 

been correctly prepared to match the voltage rating available. 

Also are in accordance with our electric wiring diagram.

6) 

Make sure that the combustion head enters the furnace to the 

extent specified by the boiler manufacturer

Check that the 

combustion head is in the position considered necessary for 

the fuel delivery required (the air passage between the disk and 

the head should be considerably closed when the fuel delivery 

is relatively reduced;  on the other hand, when the nozzle has 

a fairly high delivery, the air passage between the disk and 

the head should be relatively (see chapter “Regulation of the 

combustion head”).

7)  Remove  the  protective  cover  from  the  rotating  disk  in

-

serted  on  the  modulating  motor.  On  this  disk  have

 

been fitted adjustable screws which are used to control the fuel 

and the relative combustion air.

8)  Put the two modulating switches in the “MIN” (minimum) and 

“MAN” (manual)  positions.

9)  Start up the fuel supply auxiliary circuit, check its efficiency and 

regulate the pressure at about 1 bar (if the circuit is supplied 

with a pressure regulator).

10)Remove from the pump the vacuumeter connection point plug 

and then open slightly

 the gate valve fitted on  the fuel arrival 

pipe. Wait until fuel comes out of the hole, without air bubbles, 

and then re-close the gate valve.

11)  Insert a manometer (end of the scale about 3 bar) into the 

vacuu-

meter connection point on the pump and control the value of the 

pressure at which the fuel arrives at the burner pump.  Insert a 

manometer (and of the scale about 30 bar) into the manometer 

connection point provided on the pump and control its working 

pressure. Insert a manometer (end of the scale about 30 bar) into 

the special connection point of the first flame return pressure.

12) Now open all the gate valves and any other fuel interception 

devices fitted on the fuel pipelines.

13) Put the switch on the control panel in the “0” (open) position and 

give current to the electric lines which the burner is connected 

to. Check, by pressing manually on the relative relay, that the 

motor rotates in the right direction.  If it does not, exchange the 

places of two cables of the principle line in order to invert the 

sense of rotation.

14) Start operating the burner pump by pressing manually on the 

relative relay until the manometer, which measures the working 

pressure of the pump, indicates a slight pressure.  The presence 

of low pressure in the circuit confirms that filling up has taken 

place.

15) Insert the switch on the control panel to give current to the control 

box. If the thermostats (safety and boiler) are closed, the control 

box’s programmer will be connected and will insert the burner’s 

component devices according to its-established programme.The 

unit starts up in this way, as described in chapter “Description 

of Operations”.

16) When  the  burner  is  operating  at  “minimum”,  pro

-

ceed  with  regulating  the  air  to  the  quantity  considered

 

necessary  to ensure efficient combustion. Tighten or loosen the 

adjusting screws situated on the point of contact on the lever, 

which transmits the movement to the combustion air regulation 

shutter. It is preferable that the quantity of air for the “minimum” 

is slightly reduced, in order to ensure a soft ignition even in the 

most critical conditions.

17) After having regulated the air for the “minimum”, put the modu-

lation switches in the  “MAN” (manual) and  “MAX” (maximum) 

positions.

18) The modulation motor starts moving; wait until the disk on which 

the regulating  screws have been fitted, has reached an angle 

of about 12° (this corresponds to the space taken up by three 

screws), stop the modulation motor and return the switch to the 

“0” position.  Carry out a visual control of the flame and proceed, 

if necessary, with regulating the combustion air by operating 

as described in point 16. Subsequently, control combustion 

with the appropriate instruments and modify, if necessary, the 

previous regulation carried out after a visual control only. The 

operation described above should be repeated progressively 

(by moving forwards the disk by about 12° at a time) and modi

-

fying every time, if necessary; the fuel/air ratio during the entire 

modulating run. Make sure that the increase in fuel delivery 

occurs gradually and that maximum delivery is reached at the 

end of the modulation run. This is necessary in order to ensure 

that modulation functions with good graduality. The position of 

the screws that commend the fuel may need to be modified 

in order to obtain the graduality required. Maximum delivery 

is obtained when the return pressure is about 2 ÷ 3 bar less 

than the delivery pressure (normally 20 ÷ 22 bar). For a correct 

Fuel/air ratio, the percentage of Carbon Dioxide (CO

2

) should 

increase with the increase delivery (from a minimum of 10% at 

minimum delivery to a maximum of 13% at maximum delivery).

 

We advise against exceeding 13% of CO

2

 to avoid operating with 

a rather limited excess of air which would cause a considerable 

increase in smoke opacity due to unavoidable circumstances 

(a variation in the atmospheric pressure; presence of dust 

particles in the fan’s air ducts, etc.). Smoke opacity depends 

on the type of fuel utilized (the most recent provisions indi

-

cate that it should not exceed n. 2 of the Bacharach Scale). 

We advise, if possible, maintaining smoke opacity below n. 2 of 

the Bacharach Scale even if, as a consequence, the CO

2

 value 

is slightly lower. The lower smoke opacity dirties the boiler less 

Содержание BT 100 DSPG

Страница 1: ...EN SP 98319_200910 Maintenance use and installation manual Manual de mantenimiento uso e instalaci n BT 75 DSPG BT 100 DSPG BT 120 DSPG BT 180 DSPG BT 250 DSPG BT 300 DSPG...

Страница 2: ......

Страница 3: ...se debe desconectar antes de iniciar los trabajos Si los trabajos no son efectuados correctamente se corre el riesgo de que se produzcan accidentes peligrosos Before using the burner for the first tim...

Страница 4: ......

Страница 5: ...l oil side EN 60335 1 2001 A1 2004 A11 2004 A2 2006 EN 60335 2 102 2006 EN 50165 1997 A1 2001 EN 55014 1 2000 A1 2001 A2 2002 EN 55014 2 1997 A1 2001 EN 50366 2004 A1 2006 EN 61000 3 2 2000 A2 2005 Su...

Страница 6: ...If the equipment is sold or transferred to another owner or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new own...

Страница 7: ...out by qualified technicians and in compliance with current law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not ca...

Страница 8: ...4 16 N 4 16 FLEXIBLE PIPES N 2 1 x1 N 2 1 x1 N 2 1 x1 NIPPLES N 2 1 x1 N 2 1 x1 N 2 1 x1 FILTER 1 1 1 TECHNICAL DATA MODELS BT 180 DSPG BT 250 DSPG BT 300 DSPG FLOW RATE MIN kg h 60 74 110 MAX kg h 18...

Страница 9: ...PG MOD A A1 A2 B B1 B2 C D E F I I1 L M N MIN MAX BT 75 DSPG 595 310 385 510 365 145 1215 130 450 205 160 260 260 225 300 M12 170 BT 100 DSPG 670 330 340 525 365 160 1415 210 400 230 195 320 276 M16 2...

Страница 10: ...E N G L I S H 10 32 98319_200910 WORKING FIELD...

Страница 11: ...over the basic requirements needed to ensure efficient operations All rules and regulations existing in the country of installation should be strictly complied with and the local fire brigade should b...

Страница 12: ...C FROM 75 TO 300 DSPG The combustible recovery and degasifier tanks diameter 150 height 400 should be installed as near as possible to the burner and should be about 0 5 m higher with respect to the b...

Страница 13: ...25 Cyclic relay Safety Time in seconds 5 Pre Ventilation Oil Pre circulation Time in seconds 22 5 Pre ignition Time in seconds 2 5 Post ignition Time in seconds 5 Time between 1st flame Start of Modu...

Страница 14: ...IZER UNIT 5 RETURN NOZZLE WITHOUT PIN 6 ROD WITH CLOSING PINS 7 BY PASS HOLES 8 CLOUSING SPRING 9 OPENING ELECTROMAGNET 10 RETURN PRESSURE REGULATOR MIN 10 12 BAR MAX 18 20 BAR 11 MODULATION SERVOMOTO...

Страница 15: ...the maximum flow rate the difference in pressure between the delivery pump pressure and return pressure at the return pressure regulator pressure running to and from the nozzle must be at least 2 3 ba...

Страница 16: ...sing manually on the relative relay until the manometer which measures the working pressure of the pump indicates a slight pressure The presence of low pressure in the circuit confirms that filling up...

Страница 17: ...er is equipped with a combustion head which can be regu lated by moving it backwards or forwards in such a way as to close more or open more the air passage between the disk and the head By throttling...

Страница 18: ...f combustion head Combustion air inlet with very opened shutter Air flow quite locked Attention Avoid complete locking N BT 8608 1 GENERAL DIAGRAM AIR REGULATION INCORRECT REGULATION Combustion head A...

Страница 19: ...n the direction desired each red ring will rotate with respect to the reference scale The index of the red ring indicates on the respective reference scale the rotation angle taken up for each cam Ref...

Страница 20: ...E N G L I S H 20 32 98319_200910 Control box...

Страница 21: ...E N G L I S H 21 32 98319_200910...

Страница 22: ...E N G L I S H 22 32 98319_200910...

Страница 23: ...E N G L I S H 23 32 98319_200910...

Страница 24: ...E N G L I S H 24 32 98319_200910...

Страница 25: ...E N G L I S H 25 32 98319_200910...

Страница 26: ...E N G L I S H 26 32 98319_200910...

Страница 27: ...E N G L I S H 27 32 98319_200910...

Страница 28: ...E N G L I S H 28 32 98319_200910...

Страница 29: ...E N G L I S H 29 32 98319_200910...

Страница 30: ...E N G L I S H 30 32 98319_200910...

Страница 31: ...6 52 3 00 3 50 11 13 11 90 12 62 13 30 13 95 14 57 15 17 15 74 16 29 16 83 17 34 17 85 18 34 18 81 19 28 3 50 4 00 12 72 13 60 14 42 15 20 15 94 16 65 17 33 17 99 18 62 19 23 19 82 20 40 20 95 21 50 2...

Страница 32: ...E N G L I S H 32 32 98319_200910...

Страница 33: ...mixtos lado gas leo EN 60335 1 2001 A1 2004 A11 2004 A2 2006 EN 60335 2 102 2006 EN 50165 1997 A1 2001 EN 55014 1 2000 A1 2001 A2 2002 EN 55014 2 1997 A1 2001 EN 50366 2004 A1 2006 EN 61000 3 2 2000 A...

Страница 34: ...to hay que asegurarse siempre de que el libro de instruccionesest siempreconelaparatoparaquepuedaserconsultado por el nuevo propietario y o instalador Para todos los aparatos con elementos opcionales...

Страница 35: ...podr an comprometer el buen funciona miento del quemador La primera vez que se pone en funcionamiento el aparato el personal cualificado profesionalmente tiene que controlar a la estanqueidad en el t...

Страница 36: ...UBOS FLEXIBLES N 2 1 x1 N 2 1 x1 N 2 1 x1 CONTRARROSCA N 2 1 x1 N 2 1 x1 N 2 1 x1 FILTRO 1 1 1 CARACTIR STICAS T CNICAS MOD BT 180 DSPG BT 250 DSPG BT 300 DSPG CAUDAL MIN kg h 60 74 110 MAX kg h 180 2...

Страница 37: ...A1 A2 B B1 B2 C D E F I I1 L M N MIN MAX BT 75 DSPG 595 310 385 510 365 145 1215 130 450 205 160 260 260 225 300 M12 170 BT 100 DSPG 670 330 340 525 365 160 1415 210 400 230 195 320 276 M16 240 BT 12...

Страница 38: ...E S P A O L 6 26 98319_200910 RANGO DE TRABAJO...

Страница 39: ...ste circuito sin regulador de presi n utilizando el esquema de funcionamiento expuesto en el dibujo n BT 8666 3 Para efectuar el circuito de alimentaci n siga las instrucciones de nuestros dibujos N 0...

Страница 40: ...l quemador 1 Tanque principal 2 Filtro 3 Bomba de circulaci n 4 Descarga agua y circuito hidr ulico 5 Descarga aria gas normalmente cerrado 6 Recuperaci n combustible y desga sificador 7 V lvula unidi...

Страница 41: ...BLE EN SEGUNDOS 22 5 PREENCENDIDO EN SEGUNDOS 2 5 POST ENCENDIDO EN SEGUNDOS 5 TIEMPO ENTRE LA 1 LLA MA Y INICIO DE LA MODU LACI N EN SEGUNDOS 15 Caracter sticas de la caja de control regulada en la b...

Страница 42: ...JA 6 VARILLAS CON AGUJAS DE CIERRE 7 ORIFIC OS DE BY PASS 8 MULLES DE CIERRE 9 ELECTROIM N DE ABERTURA 10 REGULADOR DE PRESI NDE RETORNO MIN 10 12 bar MAX 18 20 bar 11 SERVOMOTOR DE MODULACI N 12 DISC...

Страница 43: ...vez En la pr ctica cuando la tobera funciona con el suministro m ximo seleccionado la diferencia de presi n entre el env o a la tobera presi n de la bomba y el retorno a la tobera presi n en el regula...

Страница 44: ...la correspondiente conexi n del regulador de la presi n de retorno de la primera llama v ase BT 8714 1 para controlar la presi n de retorno 12 Abra todas las v lvulas y otros posibles dispositivos de...

Страница 45: ...uemador c Si mantenemos la fotorresistencia en la oscuridad el quemador se vuelve a encender pero lafotorresistencia no ve la luz y tras el tiempo establecido por el programa de la caja de control se...

Страница 46: ...E S P A O L 14 26 98319_200910 N BT 8608 1 ESQUEMA DE PRINCIPIO REGULACI N DEL AIRE ESQUEMA INDICATIVO DISPOSICI N DISCO BOQUILLAS ELECTRODOS N 0002931451...

Страница 47: ...do Posici n 2 activado VISTA DEL MOTOR SQM 10 Y SQM 20 DE MANDO MODULACI N PARA REGULACI N LEVAS N BT 8562 2 Para modificar la regulaci n de las 3 levas utilizadas se opera con los respectivos anillos...

Страница 48: ...E S P A O L 16 26 98319_200910 Caya electronica de mando y control...

Страница 49: ...E S P A O L 17 26 98319_200910...

Страница 50: ...E S P A O L 18 26 98319_200910...

Страница 51: ...E S P A O L 19 26 98319_200910...

Страница 52: ...E S P A O L 20 26 98319_200910...

Страница 53: ...E S P A O L 21 26 98319_200910...

Страница 54: ...E S P A O L 22 26 98319_200910...

Страница 55: ...E S P A O L 23 26 98319_200910...

Страница 56: ...E S P A O L 24 26 98319_200910...

Страница 57: ...16 52 3 00 3 50 11 13 11 90 12 62 13 30 13 95 14 57 15 17 15 74 16 29 16 83 17 34 17 85 18 34 18 81 19 28 3 50 4 00 12 72 13 60 14 42 15 20 15 94 16 65 17 33 17 99 18 62 19 23 19 82 20 40 20 95 21 50...

Страница 58: ...E S P A O L 26 26 98319_200910...

Страница 59: ...vztxrvt fhfrbthvxbvrv 4 Ghvmjhs eghfdktyv v rjybhjk lk ujhtkjr hfmjbf ov yf vlrjc bjgkvdt 17 Ghvywvgvfknyf x tcf uvlhfdkvztxrjuj gvbfyv gjl lfdktyvtc lk lde afrtknys ujhtkjr vkv cjlekvhjdfyys yf ufpjq...

Страница 60: ...2 30 98319_200910 I BALTUR a b c a b c d e f g...

Страница 61: ...3 30 98319_200910 I 2 RC a b c d e a b a b c d...

Страница 62: ...1 x1 N 2 1 x1 N 2 1 x1 Gfbhemrv N 2 1 x1 N 2 1 x1 N 2 1 x1 Avknbh 1 1 1 Bt yvztxrvt fhfrbthvxbvrv Cjltkn BT 180 DSPG BT 250 DSPG BT 300 DSPG Hfx jl cvy ru z 60 74 110 cfrx ru z 180 270 325 Btgkjdf cjo...

Страница 63: ...240 BT 180 DSPG 815 390 425 650 450 200 1700 200 535 260 220 320 320 280 370 M12 230 BT 250 DSPG 1000 520 480 740 580 160 1700 235 560 260 220 320 320 280 370 M12 230 BT 300 DSPG 1000 520 480 800 580...

Страница 64: ...6 30 98319_200910 HFMJZVQ LVFGFPJY cmfh rDfb ru z Ufpjqkn cmfh rDfb ru z Ufpjqkn rrfk z 1 000...

Страница 65: ...bfr v ghv hfmjbf otq ujhtkrjq yf cfrxvcfknyjq gjlfzt ujh ztuj pfghjityyjq rjbkjc Lfyye xvxbtce gvbfyv cj yj dsgjkyvbn mtp htuek bjhf lfdktyv vxgjknpe ghvywvgvfknye x tce DB 8666 3 Xvxbtcf gvbfyv ljk y...

Страница 66: ...txrjuj gvbfyv gjl lfdktyvtc lk lde afrtknys ujhtkjr vkv cjlekvhjdfyys yf ufpjqkt Htpthdefhs lk gjdbjhyjuj vxgjknpjdfyv ufpjqk lvfctbh 150 dsxjbf 400 ljk ys exbfyfd kvdfbnx rfr cj yj mkv t r ujhtkrt gh...

Страница 67: ...knbfbt ztuj lfdktyvt yfxjxf exbfyfdkvdftbx yf yjhcfknyjc pyfztyvv 20 22 mfh B uv jb vcf b pfbdjhyst igvknrv jb v xtltk gjpdjk btc xfcsc bjgkvde gjxbegvbn yf ajhxeyre gjl jbhtuekvhjdfyysc yfxjxjc lfdkt...

Страница 68: ...jhf Ghvywvgvfknyf x tcf lk cjlekvhjdfyys ujhtkjr hfmjbf ov yf ufp jqkt cfuyvb ajhxeyrf mtp igvknrv N BT 8714 2 rev 19 02 2002 Ghvmjh eghfdktyv v xjjbdtbxbde ott ghjuhfcc exb xbdj Wvrkvztxrjt htkt LAL...

Страница 69: ...11 30 98319_200910 N 0002900580 BALTUR 1 4 20 22 1 4 1 4 20 22 1 4 N BT 9353 1 CB CHARLES BERGONZO 30 45 60 80 1 3 B3 1 5 B5 2 3 20 22 20 2 18 22 3 19 20 3 17 22 2 20...

Страница 70: ...j tyye yf bhemt gjldjlf ujh ztuj Ds lfbn lj bt gjh gjrf ujh ztt yt yfzytb ds jl vbn vp jbdthxbv mtp djpleiys gepshtq gjxkt ztuj pfrhsbn pfldv re 11 Exbfyjdvbn cfyjctbh ghtltk vpcthtyv jrjkj 3 mfh d uy...

Страница 71: ...sxjrvc lf t txkv XJ2 xkturf pfyv tyj Yfgjcvyftc zbj lk ghjdtltyv ghfdvknyjq htuekvhjdrv ytjm jlvcj zbjms btcg thfbehf djls d exbfyjdrt mskf d ht vct v zbjms ujhtkrf mskf d hfmjztc xjxbj yvv rfr cvyvce...

Страница 72: ...df pfrhsdf otujgjlfzedjple fyfxctxvbtknye ujkjdre d ghjct ebjzyjt gjkj tyvt drk zvd ujhtkre lk jhvtybvhjdjzyjq htuekvhjdrv rfr hfytt jgvxfyj Gjxkt ljxbv tyv tkftcjq cfrxvcfknyjq gjlfzv xk tletb ghtlex...

Страница 73: ...nyf ujkjdrf Mjknijt jbrhsbvt ghj jlyjuj jbdthxbv gjlfzv djple f Hezrv htuekvhjdfyv v avrxvhjdfyv xctxvbtknyjq ujkjdrv D jl djple f lk ujhtyv pfxkjyrf xkvirjc ghvrhsbf Xctxvbtknyf ujkjdrf Hezrv htuekvh...

Страница 74: ...rhfxyjt rjknwj dhfoftbx jbyjxvbtknyj irfkt jbxztbf Erfpfbtkn rhfxyjuj rjknwf gjrfpsdftb yf xjjbdtbxbde otq irfkt jbxztbf eujk dhfotyv exbfyjdktyysq lk rf ljuj rekfzrf D Hszfu gjlrk ztyv v vxrk ztyv xw...

Страница 75: ...17 30 98319_200910 Ghvmjhs eghfdkt yv v rjybhjk lk ujhtkjr hfmjbf ov yf vlrjc bjgkvdt...

Страница 76: ...18 30 98319_200910...

Страница 77: ...19 30 98319_200910...

Страница 78: ...20 30 98319_200910...

Страница 79: ...21 30 98319_200910...

Страница 80: ...22 30 98319_200910...

Страница 81: ...23 30 98319_200910...

Страница 82: ...24 30 98319_200910...

Страница 83: ...25 30 98319_200910...

Страница 84: ...26 30 98319_200910...

Страница 85: ...27 30 98319_200910...

Страница 86: ...28 30 98319_200910...

Страница 87: ...29 30 98319_200910...

Страница 88: ...13 60 14 42 15 20 15 94 16 65 17 33 17 99 18 62 19 23 19 82 20 40 20 95 21 50 22 03 4 00 4 50 14 31 15 30 16 22 17 10 17 94 18 73 19 50 20 24 20 95 21 63 22 30 22 95 23 57 24 19 24 78 4 50 5 00 15 90...

Страница 89: ...89 92 98319_200910 ESQUEMA ELECTRICO...

Страница 90: ...90 92 98319_200910...

Страница 91: ...OFF SWITCH INTERRUPTOR ENCENDIDO APAGADO S2 RE SET PUSH BUTTON PULSADOR DE DESBLOQUEO S4 AUT MAN SELECTOR CONMUTADOR AUTOMATICO MANUAL S5 MIN MAX COMMUTATOR CONMUTADOR MIN MAX T2 2ND STAGE THERMOSTAT...

Страница 92: ...ativo La Casa por lo tanto se reserva cualquier posibilitad de modificati n de datos t cnicos y otras anotaciones Yfxbj ovq rfbfkju vylvrfbvdty Pfdjl vpujbjdvbtkn jxbfdk tb pf xjmjq ghfdj rfr gj cjlva...

Отзывы: