ELECTRICAL CONNECTIONS
• It is advisable to make all connections with flexible electric wire.
• Conductor minimum section must be 1.5 mm².
• Electrical lines must be kept away from hot parts.
• The burner installation is allowed only in environments with
pollution degree 2 as indicated in annex M of the EN 60335-
1:2008-07 regulation.
• Make sure that the electric line to which the unit will be connected
has frequency and voltage ratings suitable for the burner.
• The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can
be accessed easily.
• The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current
absorbed by the burner.
• The mains supply connection requires an omnipolar switch
with a contact opening gap equal to or greater than 3 mm in
accordance with current safety regulations.
• Refer to the wiring diagram for electrical connections (line and
thermostats).
• Unsheathe the external insulating cover of the power cable to
the necessary extent for the connection, thus avoiding the wire
from coming into contact with metal parts.
To carry out the connection of the burner to the power supply line
proceed as follows:
• Remove the cover by unscrewing the screws (1), without
removing the transparent door. In this way the burner’s electrical
panel can be accessed.
• Loosen the screws (2) and after removing the cable clamp plate
(3), make the 7 pole plug, the 4 pole plug and the modulation
control cable come through the hole. Connect the power supply
cables (4) to the contactor, connect the cable to ground (5) and
close the cable holder.
• Reposition the cable clamp plate. Turn the cam (6) so that the
plate exerts sufficient pressure on the cables, then tighten the
screws that fasten the plate. Finally, connect the related plugs
and modulation command cable, if installed.
CAUTION / WARNING
The housings for the cables for the plugs are provided
respectively for cable Ø 9.5÷10 mm and Ø 8.5÷9 mm,
this ensures the protection rating is IP 54 (Standard IEC
EN60529) for the electrical panel.
1
1
0002934780a
Содержание BGN 300 LX
Страница 2: ......
Страница 29: ...ITALIANO 27 38 0006160050_201708 SCHEMI ELETTRICI...
Страница 30: ...ITALIANO 28 38 0006160050_201708...
Страница 31: ...ITALIANO 29 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...
Страница 33: ...ITALIANO 31 38 0006160050_201708 SCHEMI ELETTRICI...
Страница 34: ...ITALIANO 32 38 0006160050_201708...
Страница 35: ...ITALIANO 33 38 0006160050_201708 D...
Страница 36: ...ITALIANO 34 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...
Страница 37: ...ITALIANO 35 38 0006160050_201708...
Страница 38: ...ITALIANO 36 38 0006160050_201708 E E...
Страница 40: ...ITALIANO 38 38 0006160050_201708...
Страница 67: ...ENGLISH 27 38 0006160050_201708 WIRING DIAGRAMS...
Страница 68: ...ENGLISH 28 38 0006160050_201708...
Страница 69: ...ENGLISH 29 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...
Страница 71: ...ENGLISH 31 38 0006160050_201708 WIRING DIAGRAMS...
Страница 72: ...ENGLISH 32 38 0006160050_201708...
Страница 73: ...ENGLISH 33 38 0006160050_201708 D...
Страница 74: ...ENGLISH 34 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...
Страница 75: ...ENGLISH 35 38 0006160050_201708...
Страница 76: ...ENGLISH 36 38 0006160050_201708 E E...
Страница 78: ...ENGLISH 38 38 0006160050_201708...
Страница 79: ......