background image

ENGLISH

21 / 38

0006160050_201708

Reset the burner by pressing the appropriate button and readjust 

the pressure switch to a value that allows you to detect the air 

pressure during the preventilation stage.

The  gas  pressure  switches  (minimum  and  maximum)  prevent 

the burner from operating when gas pressure is not between the 

expected range.

The  minimum  value  pressure  switch  makes  use  of  the  NO 

(normally open) contact which is closed when the pressure switch 

detects a pressure higher than its own setting.

The maximum pressure switch makes use of the NC (normally 

closed) contact which is closed when the pressure switch detects 

a pressure lower than its own setting.

Adjustment  of  minimum  and  maximum  pressure  values  on  the 

pressure switches must be performed when testing the burner, on 

the basis of the pressure measured in each case.

The  triggering  (opening  of  the  circuit)  of  any  of  the  pressure 

switches when the burner is running (flame on) causes the burner 

to stop immediately.

It is essential to check that the burner is functioning correctly at the 

time of the first ignition.

Verify the flame detector operation as follows:

•  Disconnect the wire coming from the ionisation electrode;

•  Start up the burner;

•  The control box will complete the control cycle and after two 

seconds will lock the burner due to the lack of ignition flame;

•  switch off the burner;

•  Re-connect the wire to the ionisation electrode. 

•  This  test  should  also  be  conducted  with  the  burner  already 

on; when extracting the photocell from its seat, the apparatus 

should shut down immediately.

•  Check for the efficiency of the thermostats or boiler pressure 

switches (they should shut down the burner when triggered).

CAUTION / WARNING

Check that the ignition takes place properly. In the event 

that  the  mixer  is  too  far  forward,  it  may  happen  that  the 

outgoing air speed is so high that ignition is difficult. If this 

happens, the mixer must be gradually shifted back until it is 

in a position in which ignition occurs normally, and this new 

position can be regarded as the final position.

Remember 

that with a small flame, it is better to limit the amount of 

air to the amount strictly indispensable to ensure safe 

ignition even in the most difficult cases.

IONISATION CURRENT MEASUREMENT

The  maximum  ionisation  current  value  required  for  a  correct 

operation of the equipment is indicated in the wiring diagram.

The burner provides a significantly higher current and therefore 

does not normally require any checks at all.

Should  however,  the  ionisation  current  need  to  be  measured, 

a  microammeter  must  be  connected  in  series  to  the  ionisation 

electrode lead by opening the connector as illustrated in the figure.

Содержание BGN 300 LX

Страница 1: ...O Manuale istruzioni per l installazione l uso e la manutenzione IT Installation use and maintenance instruction manual EN BGN 300 LX ME BGN 300 LX ME V BGN 300 LX ME V CO BGN 300 LX ME V O2 BGN 390 L...

Страница 2: ......

Страница 3: ...e alla caldaia 13 Linea di alimentazione 14 Schema di principio bruciatori a gas 15 Collegamenti elettrici 16 Collegamenti elettrici Convertitore di Frequenza 18 Descrizione del funzionamento a due st...

Страница 4: ...k Sparkgas TBG TBL TS IBR IB Variante LX per basse emissioni NOx rispettano i requisiti minimi imposti dalle Direttive Europee 2009 142 CE D A G 2014 30 CE C E M 2014 35 CE D B T 2006 42 CE D M e sono...

Страница 5: ...dell apparecchio mese anno sono indicati sulla targa identificazione bruciatore presente sull apparecchio L apparecchio non adatto a essere usato da persone bambini compresi le cui capacit fisiche sen...

Страница 6: ...o dalla loro sede Rendere innocue quelle parti che potrebbero essere potenziali fonti di pericolo AVVERTENZE PER L AVVIAMENTO IL COLLAUDO L USO E LA MANUTENZIONE L avviamento il collaudo e la manutenz...

Страница 7: ...dell impianto sia idonea alla potenza assorbita dall apparecchio Non consentito l uso di adattatori prese multiple e o prolunghe per l alimentazione generale dell apparecchio alla rete elettrica Prev...

Страница 8: ...380 V 10 3N 380 V 10 GRADO DI PROTEZIONE IP 54 IP 54 IP 54 IP 54 RILEVAZIONE FIAMMA SONDA IONIZZAZIONE SONDA IONIZZAZIONE SONDA IONIZZAZIONE SONDA IONIZZAZIONE APPARECCHIATURA BT 320 BT 320 BT 320 BT...

Страница 9: ...380 V 10 GRADO DI PROTEZIONE IP 54 IP 54 IP 54 IP 54 RILEVAZIONE FIAMMA SONDA IONIZZAZIONE SONDA IONIZZAZIONE SONDA IONIZZAZIONE SONDA IONIZZAZIONE APPARECCHIATURA BT 320 BT 320 BT 320 BT 320 REGOLAZ...

Страница 10: ...nza motore ventilatore 11 Tensione di alimentazione 12 Grado di protezione 13 Paese di costruzione e numeri di certificato di omologazione 14 Anno di costruzione 15 16 Codice a barre matricola bruciat...

Страница 11: ...mento 6 Valvola gas di sicurezza 7 Pressostato gas di minima e controllo di tenuta gas 8 Display apparecchiatura 9 Vite di regolazione aria alla testa di combustione 10 Pressostato aria 11 Servomotore...

Страница 12: ...parecchiatura controllo ventilazione 0002939820 1 2 5 4 7 6 3 8 QUADRO ELETTRICO BRUCIATORE 1 Quadro elettrico 2 Apparecchiatura 3 Connettore 7 poli 4 Pannello sinottico 5 Contattore motore 6 Rel term...

Страница 13: ...lo D E F I I1 L M N BGN 300 LX ME 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX ME V 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX ME V CO 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX...

Страница 14: ...cco al generatore scorrevole per adattare la sporgenza della testa ai vari tipi di generatori di calore Cerniera ad apertura ambidestra per un comodo accesso alla testa di combustione con bruciatore m...

Страница 15: ...ngia di attacco 19 allentando le viti 6 la testa del bruciatore dovr penetrare nel focolare della misura consigliata dal costruttore del generatore Posizionare sul cannotto il cordone isolante 2 Fissa...

Страница 16: ...essione ed il bruciatore Questo tubo deve avere un diametro uguale o superiore al raccordo di attacco al bruciatore Per ottenere il miglior funzionamento del regolatore di pressione opportuno che lo s...

Страница 17: ...chema di principio M M 12 10 9 14 11 13 8 4 7 6 5 3 2 1 0002910950N2 A CURA DELL INSTALLATORE RAMPA GAS FORNITA DAL COSTRUTTORE 1 Valvola di intercettazione manuale 2 Giunto antivibrante 3 Filtro gas...

Страница 18: ...mative di sicurezza vigenti Per i collegamenti elettrici linea e termostati vedere il relativo schema elettrico Sguainare l isolante esterno del cavo di alimentazione nella misura strettamente necessa...

Страница 19: ...zionando i ganci in corrispondenza delle rispettive sedi 9 far scorrere lo sportellino nella direzione indicata dalla freccia fino ad avvertire un leggero scatto cos da garantire la tenuta CAUTELA AVV...

Страница 20: ...NEA IN C A Proteggere sempre il cavo di rete con fusibili Dimensionare i fusibili in base alle norme di sicurezza locali alla corretta tensione di ingresso e alla corrente nominale del convertitore di...

Страница 21: ...adio lo consente regolato ad un valore di temperatura o pressione superiore a quella esistente in caldaia i servomotori di regolazione dell erogazione aria gas iniziano a girare determinando un aument...

Страница 22: ...il senso di rotazione Inserire ora l interruttore generale L apparecchiatura di comando riceve cos tensione ed il programmatore determina l inserzione del bruciatore come descritto nel capitolo Descr...

Страница 23: ...azione avviare il bruciatore l apparecchiatura completer il ciclo di controllo e dopo due secondi mander in blocco il bruciatore per mancata fiamma di accensione spegnere il bruciatore ricollegare il...

Страница 24: ...do il bruciatore lavora su focolare pressurizzato e o ad alto carico termico CAUTELA AVVERTENZE Verificare la centratura della testa di combustione rispetto al disco la non perfetta centratura potrebb...

Страница 25: ...ti i componenti della testa di combustione siano in buono stato non deformati e privi di impurit o depositi derivanti dall ambiente di installazione e o da una cattiva combustione Nel caso si renda ne...

Страница 26: ...CI PULIZIA VENTOLA RAFFREDDAMENTO VERIFICA RUMOROSIT CUSCINETTI ANNO CAMMA MECCANICA VERIFICA USURA E FUNZIONALIT INGRASSAGGIO PATTINO E VITI ANNO LEVE TIRANTI SNODI SFERICI CONTROLLO EVENTUALI USURE...

Страница 27: ...nto alla vita attesa di seguito indicata Per condizioni operative normali si intendono applicazioni su caldaie ad acqua e generatori di vapore oppure applicazioni industriali conformi alla norma EN 74...

Страница 28: ...gas non stata adeguatamente sfogata dall aria caso di prima accensione 3 La pressione del gas insufficiente o eccessiva 4 Passaggio aria tra disco e testa troppo chiuso RIMEDIO 1 Invertire l alimentaz...

Страница 29: ...ITALIANO 27 38 0006160050_201708 SCHEMI ELETTRICI...

Страница 30: ...ITALIANO 28 38 0006160050_201708...

Страница 31: ...ITALIANO 29 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...

Страница 32: ...REGOLATORE ELETTRONICO P M PRESSOSTATO DI MASSIMA P1 CONTAORE PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA S1 INTERRUTTORE MARCIAARRESTO S2 PULSANTE SBLOCCO SG INTERRUTTORE GENERALE TA TRASFORMATORE...

Страница 33: ...ITALIANO 31 38 0006160050_201708 SCHEMI ELETTRICI...

Страница 34: ...ITALIANO 32 38 0006160050_201708...

Страница 35: ...ITALIANO 33 38 0006160050_201708 D...

Страница 36: ...ITALIANO 34 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...

Страница 37: ...ITALIANO 35 38 0006160050_201708...

Страница 38: ...ITALIANO 36 38 0006160050_201708 E E...

Страница 39: ...SSO COMANDO 0 4 20 mA I3 INGRESSO COMANDO 0 10V I4 SET POINT REMOTO 0 4 20 mA K7 REL MARCIA INVERTER K16 REL PRESENZA FIAMMA MV MOTORE VENTOLA N1 REGOLATORE ELETTRONICO P1 CONTAORE PA PRESSOSTATO ARIA...

Страница 40: ...ITALIANO 38 38 0006160050_201708...

Страница 41: ...ng range 12 Burner connection to the boiler 13 Supply line 14 Gas burner schematic diagram 15 Electrical connections 16 Frequency converter Electrical connections 18 Description of progressive two sta...

Страница 42: ...RiNOx Spark Sparkgas TBG TBL TS IBR IB Variant LX for low NOx emissions respect the minimal regulation of the European Directives 2009 142 CE D A G 2014 30 CE C E M 2014 35 CE D B T 2006 42 CE D M an...

Страница 43: ...40 C The storage time is 3 years GENERAL INSTRUCTIONS The equipment production date month year is written on the burner identification plate located on the equipment The device is not suitable to be...

Страница 44: ...control wheels from their position Render harmless any potentially dangerous parts INSTRUCTIONS FOR START UP INSPECTION USE AND MAINTENANCE Start up inspection and maintenance of the equipment must on...

Страница 45: ...le for the power absorbed by the equipment The use of adaptors multiple plugs and or extension leads to supply power from the mains to the appliance is not allowed For the connection to the mains fit...

Страница 46: ...10 3N 380 V 10 3N 380 V 10 DEGREE OF PROTECTION IP 54 IP 54 IP 54 IP 54 FLAME DETECTOR IONISATION PROBE IONISATION PROBE IONISATION PROBE IONISATION PROBE EQUIPMENT BT 320 BT 320 BT 320 BT 320 AIRFLO...

Страница 47: ...V 10 3N 380 V 10 DEGREE OF PROTECTION IP 54 IP 54 IP 54 IP 54 FLAME DETECTOR IONISATION PROBE IONISATION PROBE IONISATION PROBE IONISATION PROBE EQUIPMENT BT 320 BT 320 BT 320 BT 320 AIRFLOW REGULATIO...

Страница 48: ...11 Power supply voltage 12 Protection rating 13 Country of manufacture and homologation certificate numbers 14 Year of manufacture 15 16 Burner serial number bar code FIRST START UP RECORDING DATA Mod...

Страница 49: ...lve 6 Safety gas valve 7 Minimum gas pressure switch and gas leak control 8 Equipment display 9 Screw for regulation of the air supply to the combustion head 10 Air pressure switch 11 Air regulation s...

Страница 50: ...transformer 8 Ventilation control device 0002939820 1 2 5 4 7 6 3 8 BURNER ELECTRIC PANEL 1 Electrical panel 2 Control box 3 7 pole connector 4 Synoptic panel 5 Motor contactor 6 Thermal Relay 7 Igni...

Страница 51: ...D E F I I L M N BGN 300 LX ME 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX ME V 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX ME V CO 280 480 316 275 440 440 400 540 M20 360 BGN 300 LX ME V...

Страница 52: ...ding generator connection flange to adapt the head protrusion to the various types of heat generators Hinge opening on both sides for easy access to the combustion head when burner is installed 7 pole...

Страница 53: ...loosening the screws 6 The burner head must penetrate to the extent requested by the generator manufacturer Place the insulating rope 2 on the sleeve Anchor the the head unit to the boiler 1 using the...

Страница 54: ...is pipe must have a diameter equal to or greater than the connector to the burner To ensure optimal operation of the pressure regulator it should be applied to the horizontal pipe after the filter The...

Страница 55: ...ing the gas train principle M M 12 10 9 14 11 13 8 4 7 6 5 3 2 1 0002910950N2 RESPONSIBILITY OF THE INSTALLER GAS TRAIN SUPPLIED BY THE MANUFACTURER 1 Manual shut off valve 2 Vibration proof joint 3 G...

Страница 56: ...er to the wiring diagram for electrical connections line and thermostats Unsheathe the external insulating cover of the power cable to the necessary extent for the connection thus avoiding the wire fr...

Страница 57: ...l properly position the hooks at their hooking points 9 slide the door in the direction indicated by the arrow until you hear a click that ensures its seal CAUTION WARNING Only professionally qualifie...

Страница 58: ...CUIT A C LINE CABLE Always protect the network cable with fuses Dimension the fuses according to local safety regulations correct input voltage and rated current of the frequency converter If position...

Страница 59: ...hich go to the minimum point 200 If the second stage boiler thermostat or pressure switch allows it set to a temperature or pressure value higher than the existing value in the boiler the air gas supp...

Страница 60: ...tion Now switch on the main switch This powers on the control device and the programmer turns on the burner as described in the chapter Operation description For burner adjustment refer to the instruc...

Страница 61: ...ete the control cycle and after two seconds will lock the burner due to the lack of ignition flame switch off the burner Re connect the wire to the ionisation electrode This test should also be conduc...

Страница 62: ...ks on the combustion chamber that is pressurised and or at a high thermal load CAUTION WARNING Check that the combustion head is centred with respect to the disk An imperfect centring could cause a po...

Страница 63: ...head are in good condition have not been deformed and are free from deposits deriving from the installation environment and or from poor combustion If it is necessary to clean the outside of the combu...

Страница 64: ...C MOTORS COOLING FAN CLEANING BEARING NOISE CHECK YEAR MECHANICAL CAM CHECK OF WEAR AND OPERATION GREASING OF SLIDING BLOCK AND SCREWS YEAR LEVERS TIE RODS BALL JOINTS CHECK OF ANY WEAR COMPONENT LUBR...

Страница 65: ...notes if necessary are independent and do not refer to the expected lifespan stated below Normal operating conditions means applications on water boilers and steam generators or industrial application...

Страница 66: ...rst ignition 3 The gas pressure is insufficient or excessive 4 Air flow between disc and head too narrow REMEDY 1 Invert the ignition transformer power supply 230V side and check using an analogue mic...

Страница 67: ...ENGLISH 27 38 0006160050_201708 WIRING DIAGRAMS...

Страница 68: ...ENGLISH 28 38 0006160050_201708...

Страница 69: ...ENGLISH 29 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...

Страница 70: ...AN MOTOR N1 ELECTRONIC REGULATOR P M MAXIMUM PRESSURE SWITCH P1 HOUR METER PA AIR PRESSURE SWITCH Pm MINIMUM PRESSURE SWITCH S1 START STOP SWITCH S2 RELEASE BUTTON SG MAIN SWITCH TA IGNITION TRANSFORM...

Страница 71: ...ENGLISH 31 38 0006160050_201708 WIRING DIAGRAMS...

Страница 72: ...ENGLISH 32 38 0006160050_201708...

Страница 73: ...ENGLISH 33 38 0006160050_201708 D...

Страница 74: ...ENGLISH 34 38 0006160050_201708 BT1 BA BP I1 I2 I3 I4...

Страница 75: ...ENGLISH 35 38 0006160050_201708...

Страница 76: ...ENGLISH 36 38 0006160050_201708 E E...

Страница 77: ...mA COMMAND INLET I3 0 10V COMMAND INLET I4 0 4 20 mA REMOTE SET POINT K7 INVERTER START RELAY K16 REL PRESENZA FIAMMA MV FAN MOTOR N1 ELECTRONIC REGULATOR P1 HOUR METER PA AIR PRESSURE SWITCH Pm MINIM...

Страница 78: ...ENGLISH 38 38 0006160050_201708...

Страница 79: ......

Страница 80: ...Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e di quant altro in esso riportato Information contained in this c...

Отзывы: