ENGLISH
22 / 32
0006160059_201511
DETAIL OF THE MODULATION CONTROL MOTOR SQM 40 FOR CAM ADJUSTMENT
0002938350
1
2
3
4
I Maximum air opening (130°)
II Total air closure (burner stopped) (0°)
III Minimum air opening (lower than cam IV) (10°)
IV Ignition air opening (greater than cam III) (30°)
B = On and off lever for motor - camshaft coupling.
- Position 1 = excluded
- Position 2 = inserted
Use the corresponding rings (I - II - III....) to modify the adjustment of the cams used.