OPERATING RANGE
TBG 480MC
IMPORTANT
The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indicative of the burner-boiler com-
bination. For correct working of the burner the size of the combustion chamber must correspond to current regulations; if not the
manufacturers must be consulted.
The burner should not work outside the indicated work range.
¹) NATURAL GAS EMISSIONS
Classes defined according to Standard EN 676.
Class
NOx emissions in mg/kWh - natural
gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE EMISSIONS
CO emissions, natural gas/propane ≤ 100 mg/kWh
Class
NOx emissions in mg/kWh - pro-
pane gas
1
≤ 230
2
≤ 180
3
≤ 140