Secondary Device Functions (continued)
5.9.5 System Commands
Command Value Device Action
0x81 (129)
Application Reset
– Resets the
Voltage monitoring detection time
duration
with ISDU-index 0x58
subindex 2 to the default value 0.
0x82 (130)
Reset Factory Settings
– Resets the
Voltage monitoring detection time
duration
with ISDU-index 0x58
subindex 2 to the default value 0.
0xA5 (165)
Maintenance Reset
– Resets the
Voltage monitoring detection time
duration
with ISDU-index 0x58
subindex 2 to the default value 0.
Tab. 5-42: Voltage and current monitoring – System Commands
For an overview of all System Commands, see section 3.5
5.9.6 Events
Event Code
Event Type
Description
Device Status
0x5110
(20752)
Warning
Primary supply voltage exceeded
►
Check for deviations in the supply.
2 – Out-of-Specification
0x5111
(20753)
Warning
Primary supply voltage below minimum value
►
Check for deviations in the supply.
2 – Out-of-Specification
0x8D0B
(36107)
Warning
Overload or short circuit at pin 2
►
Check wiring.
2 – Out-of-Specification
0x8D0D
(36109)
Warning
Incorrect load/cable breakage
►
Check wiring or connected devices.
2 – Out-of-Specification
0x8D15
(36117)
Warning
Overload at pin 2
►
Check wiring.
2 – Out-of-Specification
Tab. 5-43: Voltage and current monitoring – Events
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Содержание IO-Link BES M12EH1-L01C40B-S04G-L04
Страница 2: ...www balluff com...
Страница 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Страница 96: ...www balluff com...
Страница 187: ......