86
english
Namur Standard
Name
Signal
Meaning
Ping
Blue, flashing, 3 Hz
The ping can be activated via a system command to find
the device again.
Short Circuit Pin 2 / Pin 4
Red, flashing, 3 Hz
Short circuit at pin 2 or pin 4
Teach In No Object
Red, flashing, 1 Hz
The sensor is in Teach-In mode and no object is visible.
Teaching is not possible.
Failure
Red, static
General error
Teach In
Red, static
The sensor is currently in Teach-In mode
Maintenance Required
Blue, static
Maintenance must be performed.
Functional Check
Orange, static
The device is currently being parameterized/adjusted.
Measurement is not currently possible.
Overload
Orange, flashing, 3 Hz
Overload on pin 2 / pin 4 has been detected.
Bad Signal Quality
Orange, flashing, 1 Hz
The signal quality of the measurement signal is below the
warning threshold. A reliable signal can no longer be
ensured.
Out of Specification
Yellow, flashing, 3 Hz
The device is operated outside of specifications. A
reliable measurement signal can no longer be ensured.
Function Display
Yellow, static
The object was detected / switching point is active
Communication
Green alternating with LED
off at ratio of 10:1, 1 s
period
IO-Link communication is active. The device is ready.
Ready Diagnosis On
Static green
The device is ready. Diagnosis functions are on.
Ready Diagnosis Off
Static white
The device is ready. Diagnosis functions are switched off.
Tab. 6-18: LED meaning and configuration – Namur Standard
6
System Functions (continued)
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Содержание IO-Link BES M12EH1-L01C40B-S04G-L04
Страница 2: ...www balluff com...
Страница 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Страница 96: ...www balluff com...
Страница 187: ......