Overview of IO-Link Data and Functions (continued)
Event Code Event Type
Description
Device Status
0x8D13
(36115)
Warning
One or more extreme conditions present.
0 – Device is operating properly.
0x8D15
(36117)
Warning
Overload at pin 2
►
Check wiring.
2 – Out-of-Specification
0x8D20
(36128)
Warning
Device temperature lower warning
– The set lower
temperature warning threshold is below the minimum
value.
0 – Device is operating properly
0x8D22
(36130)
Warning
Warning limit for write cycles reached – maintenance
monitoring no longer guaranteed – for information
purposes only.
0 – Device is operating properly
0x8D23
(36131)
Error
Write cycle limit reached – saving no longer ensured
– replacement recommended.
1 – Maintenance-Required
0x8D24
(36132)
Warning
Parameter write error – for information purposes
only.
0 – Device is operating properly
0x8D25
(36133)
Error
Parameters not consistent – basic settings are used,
service required.
4 – Failure
0x8DC0
(36288)
Notification
Teach-in timeout
– The current teach process took
too long and was interrupted.
0 – Device is operating properly.
Tab. 3-8: Events – Overview
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Содержание IO-Link BES M12EH1-L01C40B-S04G-L04
Страница 2: ...www balluff com...
Страница 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Страница 96: ...www balluff com...
Страница 187: ......