Switchpoint Mode
The AdSS profile only supports one switching
point (setpoint). Accordingly, only the Single Point
Mode is available in this profile.
Single Point Mode
In Single Point Mode, only one switching point (setpoint) is
defined.
Switching behavior:
– Measurement value ≥ switching point: output active
– Measurement value ≤ switching point minus a defined
hysteresis: output inactive
Fig. 4-3:
High
SP1
SP1-Hys
Low
Measurement value
Switching output
Single-Point Mode
Two-Point Mode
In Two-Point Mode, two switching points (setpoints) are
defined.
Switching behavior:
– Measurement value ≥ switching point 1: output active
– Measurement value ≤ switching point 2: output inactive
Fig. 4-4:
High
SP1
SP2
Low
Measurement value
Switching output
Two-Point Mode
4
Primary Device Functions (continued)
Window Mode
In Window Mode, two switching points (setpoints) are
defined.
Switching behavior:
– If the output is inactive and the measurement value is
greater than or equal to switching point 2 + 50% of the
set hysteresis or the measurement value is less than or
equal to switching point 1 – 50% of the set hysteresis,
the output switches to active.
– If the output is active and is less than or equal to
switching point 2 – 50% of the set hysteresis or the
measurement value is greater than switching point 1
+ 50% of the set hysteresis, the output switches to
inactive.
Fig. 4-5:
High
SP1
SP2
Hyst.
Hyst.
Low
Measurement
value
Switching output
Window Mode
Teach Process
For a successful teach-in as well to directly set a setpoint,
the following conditions must be met:
– The setpoint that is to be taught must be in the validity
range of the measurement value signal.
Additionally in Two-Point and Window Mode:
– Setpoint 1 must be greater than setpoint 2.
– The distance between the setpoints must be greater
than or equal to the minimum hysteresis.
Due to the requirements listed above, it may be
necessary to vary the order of the setpoints for a
successful teach-in.
An active teach process in indicated by illumination of the
red LED. If the red LED flashes, the currently pending
measurement value is outside of the validity range (IO-Link
process) or a manual teach was not possible.
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Содержание IO-Link BES M12EH1-L01C40B-S04G-L04
Страница 2: ...www balluff com...
Страница 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Страница 96: ...www balluff com...
Страница 187: ......