www.balluff.com
7
3
First steps
IO-Link port
M12, A-coded, female
Pin
Function
1
+24V, 1.6 A
2
Input/output
3
GND
4
IO-Link / input / output
5
n.a.
Note
For the digital sensor inputs, refer to guideline on inputs EN 61131-2, Type 2.
Note
Each output receives a maximum current of 2 A. The total current of the module
must not exceed 9 A per pin.
Note
Unused I/O ports must be provided with cover caps to comply with protection
type IP67.