3-4 Receiving & Installation
MN1213
Input Power Transformer
The UM series servo control requires an external isolation transformer that
provides an ungrounded AC power source.
•
UM controls with a 100VDC bus require 70VAC
RMS
nominal.
•
UM controls with a 150VDC bus require 105VAC
RMS
nominal.
To determine the proper size transformer (kVA rating), use this guideline:
(Rated Continuous Current) X (Bus Voltage) X (# of Axes)
+
kVARating
Example:
UM4–100–2 with 3 UM3015HS–100
(15A) X (100VDC) X (3 Axes) = 4.5kVA
This method of transformer sizing is safe and it may be a little oversized. In most
cases, servo controls are not continuously operating at full voltage and current all
the time. It is common practice to use a smaller transformer that is sized just
larger than to actual continuous voltage and current consumed by the motor(s).
Baldor has several transformers to suit your application. Identification of these
transformers is shown in Figure 3-3.
±
5% output voltage taps are provided to
accommodate variations in incoming AC voltage.
Figure 3-3 Input Transformer Identification
Phase
Blank = 3 Phase (3T)
E = Single Phase ( T)
T
–
Transformers:
XXX
kVA Rating
00.5 = 0.5 kVA
01.0 = 1 kVA
01.5 = 1.5 kVA
03.0 = 3.0 kVA
05.0 = 5.0 kVA
10.0 = 10.0 kVA
15.0 = 15.0 kVA
–
XX – XXXX
AC Input Voltage
1123 = 115 / 230 VAC
2346 = 230 / 460 VAC
Control Output
100 = 100V
150 = 150V
Table 3-1 Current and Voltage Rating By Control
Input Voltage
70 VAC
105 VAC
Control
Bus Voltage
100 VDC
150 VDC
AC Input Power
Control
# of Motors
Output Current Amps
Wire Size
Cont.
Peak
Catalog Number
Catalog Number
AWG
mm
2
One
6
15
UM2–100–1–10S
–
14
2.5
15
30
UM2–100–1–01S
UM2–150–1–01S
12
2.5
Two
6
15
UM2–100–1–20S
–
14
2.5
15
30
UM2–100–1–02S
UM2–150–1–02S
12
2.5
Three
6
15
UM4–100–2–30S
–
14
2.5
15
30
UM4–100–2–03S
UM4–150–2–03S
12
2.5
Four
6
15
UM4–100–2–40S
–
14
2.5
15
30
UM4–100–2–04S
UM4–150–2–04S
12
2.5
Five
6
15
UM6–100–2–50S
14
2.5
15
30
UM6–100–2–05S
UM6–150–2–05S
12
2.5
Six
6
15
UM6–100–2–60S
–
14
2.5
15
30
UM6–100–2–06S
UM6–150–2–06S
12
2.5
Note:
An isolation transformer is required to provide these voltages.
Содержание UM Series
Страница 2: ...UM Series DC Servo Control SERVO DRIVE Installation Operating Manual 4 00 MN1213...
Страница 4: ...ii Table of Contents MN1213...
Страница 20: ...3 10 Receiving Installation MN1213...
Страница 24: ...4 4 Adjustments Start Up MN1213...
Страница 28: ...5 4 Troubleshooting MN1213...
Страница 31: ...Specifications Product Data 6 3 MN1213...
Страница 32: ...6 4 Specifications Product Data MN1213...
Страница 33: ...Specifications Product Data 6 5 MN1213 Dimensions Inches mm UM4 shown Height 7 25 184 15...
Страница 34: ...6 6 Specifications Product Data MN1213...
Страница 38: ...A 4 Product Overview MN1213...
Страница 40: ...UM Series DC Servo Control MN1213...