6-2 Troubleshooting
MN1903
6.2 NextMove PCI indicators
6.2.1 Status and CAN LEDs
The backplate of the NextMove PCI contains four LEDs. S1 and S2
represent general status information. C1 and C2 are CAN traffic
indicators. The LEDs may illuminate red or green and can be
continuous or flashing.
LED State(s)
Meaning
All off
NextMove PCI is not powered.
All red
In hardware reset (see section 4.8).
All green,
cycling
In software reset, with no errors (see section 4.8).
All red,
cycling
In software reset, Power On Self Test (POST) error has occurred.
S1 green,
flashing
Program is running OK.
S1 red,
flashing
Program is running, but there is an initialization error.
S1 red,
flashing fast
Asynchronous error - for example, a limit switch has been activated.
S1 green,
flashing fast
Miscellaneous error - for example, the output driver board is not
working.
All green,
flashing
Updating firmware.
All red, turn off
in sequence:
C1, S1, S2, C2
POST is in operation (after reset).
C2 green,
flashing
Message received on CAN2 bus.
S1
C1
C2
S2