© 2020 Baker Hughes Company. All rights reserved
.
=
Masoneilan SVI II AP Digital Positioner Quick Start Guide | 68
Viewing Status Messages
To view SVI II AP status messages:
1. Press
+
and
*
to select VIEW ERR.
2. Observe any internal errors. For example, there should be
a RESET status caused by powering up. If the positioner
was powered without air a Position
Error
or
POSERR
can
appear.
3. Press
+
to view all faults.
4. Press
*
to return to
MANual
menu.
5. Press
+
until
CLR ERR
appears.
6. Press
*
CLR ERR
.
WAIT
appears for a second or two.
VIEW DATA Settings
Table 7
VIEWDATA Settings
Typical Setting
Optional Setting
SINGLE
DOUBLE
ATO
ATC
LINEAR
EQUAL
30
EQUAL
50
QUICK
50
CUSTOM
CAMFXE
Q
PSI
BAR
KPA
0.00
TS OFF
2.00
TS ON
4.00
SIG LO
4.00
SIG LO
20.00
SIG HI
12.00
SIG HI
English