Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
| 33
© 2020 Baker Hughes Company. All rights reserved
.
Travel Sensor Alignment
3 shows the general guidelines for travel sensor
alignment. Review the table prior to installing the SVI II AP on a
rotary valve actuator for proper alignment of the magnet.
Table 3
Travel Sensor Alignment
Rotary
Mounting
System
Stroke Direction
Magnet
Orientation
Valve
Position
Sensor
Counts
Rotary
<60° Rotation
Clockwise or coun-
terclockwise rotation
(0°)
Closed
(0%)
0 +/- 1000
>60° Rotation
Clockwise with
increasing setpoint
(-45°)
Full Open
or
Full
Closed
-8000 +/-
1500
or
+8000 +/-
1500
>60° Rotation
Counter Clockwise
rotation with increas-
ing setpoint
(+45°)
Full Open
or
Full
Closed
-8000 +/-
1500
or
+8000 +/-
1500
General Rule
for other con-
figurations
Any amount of rota-
tion Clockwise or
counterclockwise
(0°)
50%
Travel
(Mid-
Stroke)
0 +/- 1000
Содержание Masoneilan SVI II AP Series
Страница 6: ...This page intentionally left blank ...
Страница 76: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 105: ...Masoneilan SVI II AP Digital Positioner Quick Start Guide 105 2020 Baker Hughes Company All rights reserved ...
Страница 106: ... 2020 Baker Hughes Company All rights reserved Masoneilan SVI II AP Digital Positioner Quick Start Guide 106 ...
Страница 108: ...This page intentionally left blank ...
Страница 122: ...This page intentionally left blank ...
Страница 123: ...This page intentionally left blank ...