© 2020 Baker Hughes Company. All rights reserved
.
=
Masoneilan SVI II AP Digital Positioner Quick Start Guide | 58
For rotary valves with rotations greater than 60°, the magnet
assembly must be aligned as shown in Figure
NOTE
For a reciprocating globe valve, it is not necessary to
remove the positioner from the bracket. Details are
given below.
For reciprocating valves the adjustable link turnbuckle must be
parallel to the valve stem. To ensure linearity in positioning,
verify that the hole in the lever aligns with the indicating hole in
the bracket when the valve is in the closed position. Check that
the bracket is mounted using the proper holes (refer to Table
Figure 25
Magnet Orientation for Camflex with Valve Closed
Figure 26
Magnet Orientation for 90° Valve Rotation with Valve
Closed
Magnet
Axis
with
Valve
Closed
Magnet
Axis
with
Valve Closed
Clockwise to Close
Clockwise to Open
45
¬
Содержание Masoneilan SVI II AP Series
Страница 6: ...This page intentionally left blank ...
Страница 76: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 105: ...Masoneilan SVI II AP Digital Positioner Quick Start Guide 105 2020 Baker Hughes Company All rights reserved ...
Страница 106: ... 2020 Baker Hughes Company All rights reserved Masoneilan SVI II AP Digital Positioner Quick Start Guide 106 ...
Страница 108: ...This page intentionally left blank ...
Страница 122: ...This page intentionally left blank ...
Страница 123: ...This page intentionally left blank ...