XM/SM/XE MAGNETIC FLOWMETER
CREATE/MODIFY CONFIGURATION
E - 4
WBPEEUI110501A0
Input range value 1 using the number keys, then press
. Input range value 2. The
UNITS
displayed will
be those designated in the previous screens.
Make a selection using the arrow keys.
Select the engineering units for the totalizer.
Enter the proper pulse factor for the totalization
process.
Enter a value between 0.032 and 2000 ms. For driving an
electromechanical counter, the pulse width should be
about 50 ms. For high speed electronic devices a pulse
width of 0.05 ms. is common.
Enter a value between 0 and 10% of full scale. This
parameter causes the input to drop to a zero state when the
flow drops below the set value.
Make a selection using the arrow keys.
Make a selection using the arrow keys.
Make a selection using the arrow keys.
Make a selection using the arrow keys.
Key
Display
Comments
ENTER
RANGE VAL 1:.
nnn.nn UNITS
RANGE VAL 2:
nnn.nn UNITS
ENTER
ENTER
FAIL MODE:
→
LOW
HIGH
ENTER
SELECT TOT. EU:
→
l
m3
User Defined
ENTER
PULSE FACTOR:
(0.001 - 1000/EU)
nnn.nn
ENTER
PULSE WIDTH:
(0.64 - 2000 ms)
nnn.nn
ENTER
LOW FLOW CUTOFF:
(0 - 10%)
nn.nn%
ENTER
DIGITAL FILTER:
→
OFF
ON
ENTER
RESPONSE TIME:
→
NORMAL
FAST
ENTER
RANGE CONFIG:
→
2-FWD
1-FWD, 1REV
ENTER
FLOW DIRECTION:
→
FWD AND REV
FWD ONLY