AVS SMART POSITIONER
CREATE/MODIFY CONFIGURATION
A - 4
WBPEEUI110501A0
Set this to
YES
to be alerted if the actuator has not moved
for over two minutes with a change in the input signal.
NOTE:
Review product instruction for details.
Select pressure units.
Proportional tuning constant. Use numbers between 1 and
0 for small drives and numbers greater than 1 for large
drives.
NOTE:
Review product instruction for details.
Integral tuning constant. This number will usually range
from 1 to 40.
NOTE:
Review product instruction for details.
Derivative tuning constant. This number will usually
range between 2 and 70.
NOTE:
Review product instruction for details.
Move the indicator to proper selection.
Refer to the AVS Smart Positioner instruction for an
explanation of terms.
The input can be damped with a value of 1 to 5 seconds. A
value of 0 will disable this parameter.
Set the deviation alarm in % of deviation from the set
point.
Key
Display
Comments
ENTER
VALVE STUCK AL
NO
→
YES
ENTER
PRESSURE UNIT
psi
→
bars
ENTER
Kp:
Prop. Gain
nn.nn
ENTER
Ki:
Integral
nn.nn
ENTER
Kd:
Derivative
nn.nn
ENTER
INPUT SIGNAL:
→
NORMAL ACT
REVERSE ACT
ENTER
DAMPING:
(0 - 5 sec)
n secs
ENTER
DEVIATION ALARM
n.n%