INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-209A
3 - 5
DIGITAL INPUT JUMPER SETTINGS
There are eight on-board jumpers (J1 through J8) that select
the type of digital input signals (24 VDC, 125 VDC, or 120
VAC) being monitored.
1. Jumper pins 1 and 2 together to configure the inputs for
125 VDC or 120 VAC signals.
2. Jumper pins 2 and 3 together to configure the inputs for 24
VDC signals.
Inputs can be configured independently of each other; outputs
are 24 VDC only. Refer to Figure
for jumper locations.
PHYSICAL INSTALLATION
The LMM inserts into a standard INFI 90 Module Mounting
Unit (MMU) and occupies one slot. To install:
NOTE: Configure the LMM configuration switch
BEFORE installing.
1. 1.
Verify the slot assignment of the module.
2. Connect the hooded end of a termination cable (NKTU01,
NKTU02 or NKTM01) to the MMU backplane. To do this, insert
the connector into the backplane slot of the same slot assigned
to the LMM. The latches should snap securely into place. Refer
to
3. Align the module with the guide rails in the MMU; gently
slide the module in until the front panel is flush with the top
and bottom of the MMU frame.
4. Push and turn the two captive retaining screws on the
module faceplate one half turn to the latched position. It is
latched when the slots on the screws are vertical and the open
ends face the center of the module. (To remove the module,
turn the module retaining screws to the unlatched position
and gently slide it out).
Termination Unit/Module Configuration
The termination unit is the interface between process I/O and
the module. Several different types are used with the logic
master module. The type of I/O and slave module used are the
criteria for selecting one of the following:
NTDI01
General purpose digital I/O; interfaces field digital I/O.
NTDO02
Connects field wiring from AC or DC loads to solid state relays
driven by the IMDSM05 or IMDSO04.