INSTALLATION
CONFIGURATION
I-E96-209A
3 - 7
Cable Connections
Three cables connect the I/O to the LMM. The cable required
depends on the associated hardware being used to provide
support for the LMM functions.
•
Digital inputs/outputs from an NTDI01 or NTDO02 Termi-
nation Unit to the LMM.
•
Digital inputs/outputs from an NIDI01 or NIDO01 Termi-
nation Module to the LMM.
CONFIGURATION
Once the LMM is installed, a configuration must be defined to
determine the operations an LMM performs on its input sig-
nals. The description and operation section explains the func-
tion codes available to configure a Logic Master Module
(IMLMM02). For further explanation of these function codes
and their specifications, or further explanation of function
blocks and configurations, refer to the
.
NOTE: The NVRAM should be initialized BEFORE entering a con-
figuration into the module. This can be done using the operator
interface or the module address switch (S2).
Use an operator interface (EWS, OIS, etc.) to enter a configura-
tion into module memory. The module must be placed in con-
figure mode to enter values into function code specifications.
After entering all values, change the mode to execute. If any
errors exist in the configuration, the module will not go into
execute. Instead, the status LED will continue to blink green
and the operator interface will indicate error mode. The cause
of the configuration error can be determined by reading status
information from the LMM. Refer to the product instruction for
the operator interface you are using for procedures to change
mode, configure a module and view status messages.