TROUBLESHOOTING
STATUS BYTES
I-E96-209A
5 - 3
Table 5-2. Module Status Bytes (continued)
Field
Field Size or Value
Description
BYTE 1
ES
MODE
TYPE
80
60
1F
Error Summary (0=OK, 1=ERRORS), 11=EXT)
Module Mode (00=CFG, 10=ERR
Module Type Code =(C)
16
BYTE 2
FTX
MOV
RIO
LIO
EEF
EEI
DLS
80
40
20
10
04
02
01
First Time in Execute (0=NO, 1=YES)
Memory Overflow (0=NO, 1=YES)
Summary Remote Input Status (0=OK, 1=BAD)
Summary Local Input Status (0=OK, 1=BAD)
Summary NVRAM Failure State (0=OK, 1=BAD)
Summary NVRAM Initialized State (0=OK, 1=BAD)
Digital Logic Station Status (0=GOOD, 1=BAD)
BYTE 3-5
3
4
5
NVRAM Error: Write Failure
Checksum Failure
Bad Data
Reset During Write
MISSING SLAVE MODULE
(1), (2) = Slave Address
CONFIGURATION ERROR - UNDEFINED BLOCK
(1), (2) = Block Making Reference
CONFIGURATION ERROR - INPUT DATA TYPE IS INCORRECT
(1), (2) = Block Making Reference
INSUFFICIENT MEMORY IN REMOTE MODULE
(1), (2) = Block Number of Digital Input List
TRIP BLOCK ACTIVATED
(1), (2) = Block Number of TRIP Block
TOO MANY SEGMENT CONTROL BLOCKS
CONFIGURATION ERROR - SEQUENCING TOO COMPLEX
01
03
05
06
07
08
0A
0C
01
02
03
FF
(1)
(1)
(1)
(1)
(1)
-
-
-
-
-
-
(2)
(2)
(2)
(2)
(2)
-
-
NOTE:
All numbers in bytes 4 and 5 are encoded in BCD with (1) = most significant byte and (2) = least significant byte.
Example:
Block number 1024, (1) = 10, (2) = 24.