OPERATING PROCEDURES
OPERATION
4 - 2
WBPEEUI240756A0
®
OPERATION
Normal operation begins after the FEC module completes the
communication checks of all input channels. During opera-
tion, the function code specifications can be tuned through an
INFI 90 OPEN operator interface. Refer to the
for more information on function code
132 (analog input) and function code 133 (smart transmitter
definition).
NOTE: On-line configuration changes which affect the mode of
operation are not supported for function codes 132 and 133. A mode
change (reset) of the MFP or FEC module may be required for
changes to take effect.
For IMFEC11 modules, smart transmitter parameters can be
viewed or modified using the handheld Type STT02/03 smart
transmitter terminal. View only is possible when the FEC mod-
ule is present and the FEC channel is on-line. View or modify is
possible without the FEC module present or when the FEC
channel is off-line. Figure
shows how the Type STT02/03
terminal connects to the NTFB01 termination unit.
Figure 4-1. Connecting the Type STT02/03 Terminal
to the NTFB01 Termination Unit
NTFB01
NKSL01
P1
P1
TP1 TP2
P2
P3
STT02/03
T00919A
IMFEC1