3Power connections
Page 8/43
UF_iS4000_BA_02_1811
RS-Interface
Dig. Out- and Input
Analog Output
Solid State Relay
RS-Interface
DIP switch
Display
Sensor input
Configuring input/output (I/O)
Input/Output
Description
Terminal
Analog output*
0 - 20 mA
4 - 20 mA
RL < 800 Ohm
0 - 10 mA
7 (+)
8 (-)
9 (GND)
Digital output
1*
Open collector max. 10 kHz
•
Passive max. 32 VDC, <100 Hz 100 mA, >100 Hz 20 mA
•
Active 24 VDC, 20 mA
(can be powered by analog output if not used)
3 (-)
4 (+)
2*
Open collector max. 10 kHz
•
Passive max. 32 VDC, <100 Hz 100 mA, >100 Hz 20 mA
•
Active 24 VDC, 20 mA
(can be powered by analog output if not used)
1 (-)
2 (+)
3
Solid State Relais max. 230 VAC, 500 mA, max 1 Hz
(Function is linked with Output 2)
S1 and
S2
Digital input*
5 - 30 VDC
5 (-) and 6 (+)
RS interfaces*
RS232, RS485 and RS422 with ModBus
®
RTU.
Mode can be configured by DIP switches also termination
ON or OFF.
In case of the RS485 the A wire has to be
connected to Y terminal and the B wire has to be
connected to Z terminal.
422
232
485
A
RxD
B
Z
TxD
B
Y
A
G (GND)
USB
USB Device CDC (Host Mass Storage)
Micro USB
Ethernet*
Ethernet Interface connection
RJ45 socket
* all marked in- and outputs are according to safety data TNV-1 IEC 60950-1
Auxiliary power
USB