Badger Meter 220 Series Скачать руководство пользователя страница 8

Example

: The sensor is installed in an 8 inch schedule 80 pipe, with a pipe wall thickness of 1/2 inch . If the overall sensor 

length is 16-3/8 inches and the H dimension is 10 inches, the D value is calculated as follows:

D =     Overall length  −  (H +  pipe wall thickness  +  Insertion Depth) 

D =                16-3/8 in.  −  (10 in.     +      1/2 in.       +        1-1/2 in.)  

D =                16-3/8 in.  −    12 in.  

                                                                     D =                   4-3/8 in.

   

BLEED PETCOCK

HEX NUT

JAM NUT

Figure 4:  Sensor parts

1 .  Set one set of the hex/jam nuts so that the distance between the top surface of the hex nut and the top surface of the hex 

mounting adaptor is equal to the D dimension calculated above . 

2 .  Then adjust the other two sets of hex/jam nuts 1-1/2 inches (38 mm) below the first jam nut to allow clearance for the 

Model HTT (Hot Tap Tool) top yoke .

3 .  Fully extend the HTT by turning the drive nut counterclockwise with a 15/16 inch socket or box wrench (customer 

supplied) until the drive nut contacts the tool . Slide the positioning collar into the tool top yoke . 

4 .  Remove the HTT split ring and clevis pin and slide the tool bottom yoke into the groove on the sensor hex mounting 

adaptor . Secure by replacing the clevis pin and split ring .

5 .  Mark the sleeve 2-3/4 inches (51 mm) from the impeller end of the metal sleeve . This mark is a stopping point to prevent 

the impeller/bearing from being damaged . 

6 .  Open the bleed petcock valve on the hex mounting adapter to relieve the pressure resulting from the flow sensor  

sleeve insertion . 

7 .  Carefully hand insert the hot tap flow sensor sleeve assembly into the hex mounting adapter until the mark lines up with 

the top of the hex mounting adapter . At this point, the sleeve will have been inserted past the top two O-rings in the 

adapter, approximately 1…1-1/4 inches (25…32 mm) . Take care not to push the sensor past the mark on the sleeve as the 

impeller could be damaged if it strikes the closed valve .

8 .  Rotate the HTT so the threaded rod with the adjusted hex/jam nuts is centered in the top yoke of the hot tap tool .
9 .  Rotate the sensor sleeve so the positioning collar holes align with the threaded rods and flow direction label is in general 

direction making sure the positioning collar is located in the recessed area of the top yoke . 

10 . Slide the top yoke of the HTT over the positioning collar and secure by tightening the two thumbscrews on top of 

the yoke .

11 . Close the bleed petcock and slowly open the isolation valve .
12 . Slowly turn the 15/16 inch drive nut clockwise to insert the sensor sleeve assembly through the valve and into  

the pipeline . 

13 . Carefully guide the three threaded studs of the hex mounting adapter through the holes of the sensor positioning collar . 
14 . Carefully lower the sensor until the positioning collar contacts the hex nut preset for the correct depth adjustment . 

Hot Tap Installation for 225BR, 226BR, and 226SS

Page 8 

February 2018

SEN-UM-01635-EN-11

Содержание 220 Series

Страница 1: ...Flow Sensors Insertion Style Flow Sensors Series 220 225 226 SEN UM 01635 EN 11 February 2018 User Manual...

Страница 2: ...is Depressurized and Drained 7 Installation into a Pressurized Pipeline 7 Electrical Installation 10 Standard Sensors 10 IR Sensors 10 High Temperature Sensors 11 Electrical Installation Safety 11 Ca...

Страница 3: ...y dependent on proper location in the piping system Irregular flow velocity profiles caused by valves fittings and pipe bends can lead to inaccurate overall flow rate indications although local flow v...

Страница 4: ...or inserted 1 1 2 inches 38 mm into the pipe flow To determine the proper insertion depth follow these steps 1 Apply anti seize thread lubricant supplied with the sensor to the threaded studs of the m...

Страница 5: ...S 2 As a backup to the flow arrow label there is a small hole next to the larger sight hole of the upstream side With a 3 32 inch Allen wrench tighten the positioning collar set screws 3 Double check...

Страница 6: ...the hex nuts 14 7 8 inches 378 mm minus the thickness of the pipe from the outside diameter of the pipe For example measure the wall thickness of the pipe from the coupon removed when the 1 7 8 inch...

Страница 7: ...pressure that may have built up b Fully open the isolation valve c Push the sensor sleeve into the pipe with a slight twisting motion d Guide the sensor collar holes over the three hex adapter studs...

Страница 8: ...valve on the hex mounting adapter to relieve the pressure resulting from the flow sensor sleeve insertion 7 Carefully hand insert the hot tap flow sensor sleeve assembly into the hex mounting adapter...

Страница 9: ...of the positioning collar with a 3 32 inch Allen wrench 19 Align the sensor sight holes along the pipe axis using the alignment rod from the sensor installation kit Make sure the flow label arrow on t...

Страница 10: ...O NOT remove the plastic caps from the sensor leads until ready to splice 1 Use a twisted pair cable suitable for direct burial to connect the sensor to the transmitter monitor or controller Multi pai...

Страница 11: ...afe when installed in conformance with Badger Meter installation drawing 06 480 002 Figure 5 as specified on the blue label identifying an intrinsically safe sensor Entity approval implies that only t...

Страница 12: ...OF BADGER METER TOLERANCE ON 4 PLACE DIMENSIONS 0025 0635 THIS DRAWING TO BE USED WITH CAD MODEL WHEN SUPPLIED BY BADGER METER FOR COMPLETE PRODUCT DEFINITION PER ANSI Y14 41 2003 DRAWING AND TOLERANC...

Страница 13: ...mns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensors By substi...

Страница 14: ...3 21 068 0 256 50 1500 8 inch Sch 10S 8 625 8 329 43 914 0 286 80 2500 Sch 20 8 625 8 125 41 653 0 283 80 2500 Sch 30 8 625 8 071 41 063 0 283 80 2500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2500 Sc...

Страница 15: ...511 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24...

Страница 16: ...letely out The impeller assembly will now be free and will drop out 5 Inspect the shaft and bearings for wear and replace as necessary 6 See Figure 5 To reinstall position the impeller in the cavity o...

Страница 17: ...terminals ON and OFF repeatedly allows the display to respond by trying to calculate a flow rate for the frequency of your shorting action If the display does not show a change from 0 00 it indicates...

Страница 18: ...100 psi 68 F Recommended Design Flow Range 0 5 30 ft sec Initial detection below 0 3 ft sec Accuracy 1 0 of full scale over recommended design flow range Repeatability 0 3 of full scale over recommend...

Страница 19: ...User Manual INTENTIONAL BLANK PAGE Page 19 February 2018 SEN UM 01635 EN 11...

Страница 20: ...Meter Slovakia s r o Racianska 109 B 831 02 Bratislava Slovakia 421 2 44 63 83 01 Asia Pacific Badger Meter 80 Marine Parade Rd 21 06 Parkway Parade Singapore 449269 65 63464836 China Badger Meter 7 1...

Отзывы: