INSTALLATION FOR 220BR, 220SS, 220PV

Installation Procedure

The insertion depth and alignment of the flow sensor assembly are critical to the accuracy of the flow measurement . The flat 

end of the sensor sleeve assembly 

MUST BE INSTALLED

 1-1/2 inches (38 mm) from the inside wall of the pipe . To allow for 

variations in wall thickness, lining, or coatings, the depth adjustment is controlled by the position of the hex nuts on the three 

threaded studs of the hex mounting adapter . The hex mounting adapter is provided with a 2 inch male NPT connection .
There are two methods of mounting these sensors in a 2-1/2 inch or larger pipe . One is with a 2 inch NPT threaded pipe 

saddle . The other is with a welded-on fitting such as a Thredolet®, also tapped for a 2 inch NPT connection . In either case, cut a 

2 inch (51 mm) hole through a depressurized pipe and then secure the saddle or weld-on fitting to the pipe . (For drilling into 

a pressurized pipe, see 

"Installation into a Pressurized Pipeline" on page 7

 .) Install the 2 inch NPT adapter provided, using a 

thread sealant to prevent leakage . Tighten as necessary . Badger Meter insert style flow sensors are calibrated with the sensor 

inserted 1-1/2 inches (38 mm) into the pipe flow . 
To determine the proper insertion depth, follow these steps:
1 .  Apply anti-seize thread lubricant (supplied with the sensor) to the threaded studs of the mounting adapter .
2 .  Insert the depth gauge into the mounting adapter and set it against the inside wall of the pipe as shown in 

Figure 1

 . Set 

the top of the upper adjusting nut to 3-3/4 inches (95 mm) as measured . Lock it in place with the bottom nut on the same 

stud . Repeat for the other adjusting nuts .

OTEE:

N

For Model 220PVS, set the nuts 6-1/2 inches (165 mm) above the inside wall of the pipe .

 

3 ¾”

2

03

45

Adjusting Nuts

Figure 1:  Installation for 220BR and 220SS

3 .  Clean the O-rings and the flow sensor sleeve, and lightly lubricate the O-rings with silicone grease from the packet 

provided (or another acceptable lubricant) . Take care not to get grease on the impeller or bearing .

4 .  Insert the flow sensor into the 2 inch NPT adapter so that the mounting holes in the positioning collar fit over the studs on 

the adapter . 

5 .  Lower the sensor onto the previously adjusted nuts . Install the lock nuts on top of the positioning collar and tighten . Now 

tighten the lower jam nuts firmly against the upper adjusting nuts to secure them for future removal of the sensor for 

inspection or service .

Installation for 220BR, 220SS, 220PV

Page 4 

February 2018

SEN-UM-01635-EN-11

Содержание 220 Series

Страница 1: ...Flow Sensors Insertion Style Flow Sensors Series 220 225 226 SEN UM 01635 EN 11 February 2018 User Manual...

Страница 2: ...is Depressurized and Drained 7 Installation into a Pressurized Pipeline 7 Electrical Installation 10 Standard Sensors 10 IR Sensors 10 High Temperature Sensors 11 Electrical Installation Safety 11 Ca...

Страница 3: ...y dependent on proper location in the piping system Irregular flow velocity profiles caused by valves fittings and pipe bends can lead to inaccurate overall flow rate indications although local flow v...

Страница 4: ...or inserted 1 1 2 inches 38 mm into the pipe flow To determine the proper insertion depth follow these steps 1 Apply anti seize thread lubricant supplied with the sensor to the threaded studs of the m...

Страница 5: ...S 2 As a backup to the flow arrow label there is a small hole next to the larger sight hole of the upstream side With a 3 32 inch Allen wrench tighten the positioning collar set screws 3 Double check...

Страница 6: ...the hex nuts 14 7 8 inches 378 mm minus the thickness of the pipe from the outside diameter of the pipe For example measure the wall thickness of the pipe from the coupon removed when the 1 7 8 inch...

Страница 7: ...pressure that may have built up b Fully open the isolation valve c Push the sensor sleeve into the pipe with a slight twisting motion d Guide the sensor collar holes over the three hex adapter studs...

Страница 8: ...valve on the hex mounting adapter to relieve the pressure resulting from the flow sensor sleeve insertion 7 Carefully hand insert the hot tap flow sensor sleeve assembly into the hex mounting adapter...

Страница 9: ...of the positioning collar with a 3 32 inch Allen wrench 19 Align the sensor sight holes along the pipe axis using the alignment rod from the sensor installation kit Make sure the flow label arrow on t...

Страница 10: ...O NOT remove the plastic caps from the sensor leads until ready to splice 1 Use a twisted pair cable suitable for direct burial to connect the sensor to the transmitter monitor or controller Multi pai...

Страница 11: ...afe when installed in conformance with Badger Meter installation drawing 06 480 002 Figure 5 as specified on the blue label identifying an intrinsically safe sensor Entity approval implies that only t...

Страница 12: ...OF BADGER METER TOLERANCE ON 4 PLACE DIMENSIONS 0025 0635 THIS DRAWING TO BE USED WITH CAD MODEL WHEN SUPPLIED BY BADGER METER FOR COMPLETE PRODUCT DEFINITION PER ANSI Y14 41 2003 DRAWING AND TOLERANC...

Страница 13: ...mns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensors By substi...

Страница 14: ...3 21 068 0 256 50 1500 8 inch Sch 10S 8 625 8 329 43 914 0 286 80 2500 Sch 20 8 625 8 125 41 653 0 283 80 2500 Sch 30 8 625 8 071 41 063 0 283 80 2500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2500 Sc...

Страница 15: ...511 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24...

Страница 16: ...letely out The impeller assembly will now be free and will drop out 5 Inspect the shaft and bearings for wear and replace as necessary 6 See Figure 5 To reinstall position the impeller in the cavity o...

Страница 17: ...terminals ON and OFF repeatedly allows the display to respond by trying to calculate a flow rate for the frequency of your shorting action If the display does not show a change from 0 00 it indicates...

Страница 18: ...100 psi 68 F Recommended Design Flow Range 0 5 30 ft sec Initial detection below 0 3 ft sec Accuracy 1 0 of full scale over recommended design flow range Repeatability 0 3 of full scale over recommend...

Страница 19: ...User Manual INTENTIONAL BLANK PAGE Page 19 February 2018 SEN UM 01635 EN 11...

Страница 20: ...Meter Slovakia s r o Racianska 109 B 831 02 Bratislava Slovakia 421 2 44 63 83 01 Asia Pacific Badger Meter 80 Marine Parade Rd 21 06 Parkway Parade Singapore 449269 65 63464836 China Badger Meter 7 1...

Отзывы: