Badger Meter 220 Series Скачать руководство пользователя страница 7

Installation if the Pipe is Depressurized and Drained

1 .  Drill or cut a hole in the pipe with a 1-7/8 inch (48 mm) drill or hole saw . Note the pipe wall thickness for use in calculating 

sensor assembly depth . A location on the top of the pipe is best for overall performance and service life; however, 

any radial location on the top half of the pipe is acceptable . Allow a minimum of 10 pipe diameters upstream and 5 

downstream from the sensor of straight unobstructed pipe to allow full development of the flow profile .

2 .  Install either a service saddle or welded pipe fitting (2 inch female NPT) on the outside diameter of the pipe over the 1-7/8 

inch (48 mm) hole .

3 .  Install the Badger Meter isolation valve and nipple onto the fitting using pipe thread sealant or Teflon® tape on all threads .
4 .  Install the Badger Meter hex mounting adapter onto the valve assembly . Use pipe thread sealant on the adapter . 
5 .  Tighten the hex mounting adapter so that no stud is aligned with the center-line of the pipe . This could interfere with final 

sensor alignment . 

6 .  Measure the depth and set the height of the nuts of the hex mounting adapter .

OTEE:

N

Badger Meter recommends that you purchase a Hot Tap insertion/removal Tool (Model HTT) for future service, 

even if the sensor is installed in a drained system . The Model HTT allows you to remove the sensor sleeve 

assembly from the pipe line without draining the entire loop where the sensor is mounted . 

7 .  In a fully depressurized and drained pipe, the sensor tube assembly may be installed by hand . If reinstalling into a drained 

system thought to have been depressurized and drained, verify by very slowly opening the isolation valve .
a .  Carefully and very slowly open the isolation valve to relieve any pressure that may have built up . 
b .  Fully open the isolation valve . 
c .  Push the sensor sleeve into the pipe with a slight twisting motion . 
d .  Guide the sensor collar holes over the three hex adapter studs until the collar rests on the nuts . Hex nuts should have 

been previously set to the correct height . 

e .  Install the three lock nuts onto these studs at the top of the positioning collar and securely tighten .

8 .  Loosen the two set screws in the positioning collar with a 3/32 inch Allen wrench . 
9 .  Align the sensor sight holes along the pipe axis using the alignment rod from the sensor installation kit . M
10 . Verify that the flow label arrow on the sensor matches the liquid flow direction inside the pipe . 
11 . Tighten the positioning collar set screws . 

OTEE:

N

As a backup to the flow label arrow, there is a small hole located beside one of the sight holes to also indicate the 

upstream side of the sensor . 

Installation into a Pressurized Pipeline

The Model HTT (Hot Tap Tool) provides the mechanical 

advantage required to safety insert and remove a 

Badger Meter hot tap flow sensor from line pressure, and 

provides a restraint when removing the sensor from a 

pressurized pipe . 
Refer to 

Figure 3 

for identification and location of the HTT 

parts described in this section . 
For pipe sizes 2-1/2 inch and above, all Badger Meter sensors 

are inserted 1-1/2 inches (38 mm) from the inside wall of the 

pipe . The insertion depth is controlled by the position of the 

hex nuts on the three threaded rods . 
To calculate the distance (D) between the top of the sensor 

hex mounting adapter and the bottom of the positioning 

collar (the top of the hex nut), 

ADD

 the H dimension, pipe 

wall thickness, and insertion depth, and 

SUBTRACT

 the total 

from the overall sensor length . See the example and formula 

on the next page, and refer to 

Figure 4

 .

Figure 3:  Model HTT (Hot Tap Tool)

Hot Tap Installation for 225BR, 226BR, and 226SS

Page 7 

February 2018

SEN-UM-01635-EN-11

Содержание 220 Series

Страница 1: ...Flow Sensors Insertion Style Flow Sensors Series 220 225 226 SEN UM 01635 EN 11 February 2018 User Manual...

Страница 2: ...is Depressurized and Drained 7 Installation into a Pressurized Pipeline 7 Electrical Installation 10 Standard Sensors 10 IR Sensors 10 High Temperature Sensors 11 Electrical Installation Safety 11 Ca...

Страница 3: ...y dependent on proper location in the piping system Irregular flow velocity profiles caused by valves fittings and pipe bends can lead to inaccurate overall flow rate indications although local flow v...

Страница 4: ...or inserted 1 1 2 inches 38 mm into the pipe flow To determine the proper insertion depth follow these steps 1 Apply anti seize thread lubricant supplied with the sensor to the threaded studs of the m...

Страница 5: ...S 2 As a backup to the flow arrow label there is a small hole next to the larger sight hole of the upstream side With a 3 32 inch Allen wrench tighten the positioning collar set screws 3 Double check...

Страница 6: ...the hex nuts 14 7 8 inches 378 mm minus the thickness of the pipe from the outside diameter of the pipe For example measure the wall thickness of the pipe from the coupon removed when the 1 7 8 inch...

Страница 7: ...pressure that may have built up b Fully open the isolation valve c Push the sensor sleeve into the pipe with a slight twisting motion d Guide the sensor collar holes over the three hex adapter studs...

Страница 8: ...valve on the hex mounting adapter to relieve the pressure resulting from the flow sensor sleeve insertion 7 Carefully hand insert the hot tap flow sensor sleeve assembly into the hex mounting adapter...

Страница 9: ...of the positioning collar with a 3 32 inch Allen wrench 19 Align the sensor sight holes along the pipe axis using the alignment rod from the sensor installation kit Make sure the flow label arrow on t...

Страница 10: ...O NOT remove the plastic caps from the sensor leads until ready to splice 1 Use a twisted pair cable suitable for direct burial to connect the sensor to the transmitter monitor or controller Multi pai...

Страница 11: ...afe when installed in conformance with Badger Meter installation drawing 06 480 002 Figure 5 as specified on the blue label identifying an intrinsically safe sensor Entity approval implies that only t...

Страница 12: ...OF BADGER METER TOLERANCE ON 4 PLACE DIMENSIONS 0025 0635 THIS DRAWING TO BE USED WITH CAD MODEL WHEN SUPPLIED BY BADGER METER FOR COMPLETE PRODUCT DEFINITION PER ANSI Y14 41 2003 DRAWING AND TOLERANC...

Страница 13: ...mns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensors By substi...

Страница 14: ...3 21 068 0 256 50 1500 8 inch Sch 10S 8 625 8 329 43 914 0 286 80 2500 Sch 20 8 625 8 125 41 653 0 283 80 2500 Sch 30 8 625 8 071 41 063 0 283 80 2500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2500 Sc...

Страница 15: ...511 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24...

Страница 16: ...letely out The impeller assembly will now be free and will drop out 5 Inspect the shaft and bearings for wear and replace as necessary 6 See Figure 5 To reinstall position the impeller in the cavity o...

Страница 17: ...terminals ON and OFF repeatedly allows the display to respond by trying to calculate a flow rate for the frequency of your shorting action If the display does not show a change from 0 00 it indicates...

Страница 18: ...100 psi 68 F Recommended Design Flow Range 0 5 30 ft sec Initial detection below 0 3 ft sec Accuracy 1 0 of full scale over recommended design flow range Repeatability 0 3 of full scale over recommend...

Страница 19: ...User Manual INTENTIONAL BLANK PAGE Page 19 February 2018 SEN UM 01635 EN 11...

Страница 20: ...Meter Slovakia s r o Racianska 109 B 831 02 Bratislava Slovakia 421 2 44 63 83 01 Asia Pacific Badger Meter 80 Marine Parade Rd 21 06 Parkway Parade Singapore 449269 65 63464836 China Badger Meter 7 1...

Отзывы: