MVR-300™ Refrigerant Gas Detector
P/N: 6203-9000 Version 1
41
Reg
Addr
Name
Description
Data
Type
Def
Val
R/W
4013
Manual
Override
Setting this flag places the detector into
manual override mode to allow for testing of
outputs. During manual override mode the
relays, analog output and LEDs will not
respond to gas events, alarm conditions or
faults.
Manual override mode may be terminated by
clearing this flag. Alternatively the mode will
timeout after a set period after which normal
operation will resume.
Boolean
0
R. W if
un-
locked
4014
Relay 1 Manual
Control
If the detector is in manual override mode,
setting this flag energizes relay 1; clearing
this flag de-energizes relay 1.
Relay failsafe configuration has no effect on
this test.
Boolean
0
R. W if
un-
locked
4015
Relay 2 Manual
Control
If the detector is in manual override mode,
setting this flag energizes relay 2; clearing
this flag de-energizes relay 2.
Relay failsafe configuration has no effect on
this test.
Boolean
0
R. W if
un-
locked
4016
Buzzer Test
Mode
If the detector is in manual override mode,
setting this flag activates the buzzer; clearing
this flag deactivates the buzzer.
Buzzer mute control has no effect on this
test.
Boolean
0
R. W if
un-
locked
4017
Red LED
Manual Control
If the detector is in manual override mode,
setting this flag turns on the red LED;
clearing this flag turns off the red LED.
Boolean
0
R. W if
un-
locked
4018
Green LED
Manual Control
If the detector is in manual override mode,
setting this flag turns on the green LED;
clearing this flag turns off the green LED.
Boolean
0
R. W if
un-
locked
4019
Analog Output
Manual Control
If the detector is in manual override mode,
setting this flag sets the analog output to full
scale; clearing this flag sets the analog
output to zero.
Boolean
0
R. W if
un-
locked