MVR-300™ Refrigerant Gas Detector
P/N: 6203-9000 Version 1
21
4.3
Other Switch Configurations
4.3.1
Reset (Cycle Power) - Switch 1
Use the following procedure to cycle power to the MVR-300.
Step
Description
1.
Move switch 1 to the ON position.
2.
Move switch 1 to the OFF position.
3.
Power is cycled to the MVR-300.
4.3.2
Reset to Factory Default Values - Switch 8
Use the following procedure to reset all configurable Modbus registers to their factory default values.
Step
Description
1.
Ensure that the detector is off. If the detector is on, turn off power.
2.
Set switch 8 to ON.
3.
Turn on the detector. The buzzer will be ON and the LED will be OFF.
4.
Set switch 8 to OFF. The buzzer will be OFF and the LED will be OFF.
5.
Using the magnetic wand, hold magnetic switch 1 (
●
) for 60 seconds. LED is GREEN during
this period.
6.
Wait for the LED to changes to ORANGE.
7.
Reset the detector by cycling power (by toggling switch 1).
8.
Detector will start-up as normal and re-read all switch settings.