MVR-300™ Refrigerant Gas Detector
18
P/N: 6203-9000 Version 1
Figure 15. Default Alarm Generation
4.2.2
Alarm Delay – Switches 2 and 3
To avoid premature alarms, ensuring the presence of refrigerant for a certain amount of time, the
triggering of the alarm can be delayed for a short period of time. Unless the alarm condition is present for
at least the delay time, the alarm will not be triggered.
Figure 16. Alarm ON Delay (Alarm Condition Must Be Present for at Least the Programmed Time)