TWIN-CHANNEL GAS 

ALARM

 

USER MANUAL

 

Содержание Twin Channel Gas Alarm

Страница 1: ...Gas Detection Specialists TWIN CHANNEL GAS ALARM USER MANUAL...

Страница 2: ......

Страница 3: ...5 2 2 Liquid Petroleum Gas Sensor 7 2 3 Technical Specification 8 3 Installation 9 3 1 Wiring 10 3 2 Pin Definitions 11 4 Initialisation Testing 12 4 1 Initialisation 12 4 2 Testing 13 5 Alarm 14 6 Tr...

Страница 4: ...ion on any operational queries or troubleshooting issues you may have The Twin Channel Gas Alarm is ideal for small and medium sized vessels as it supports two LPG sensors This product range provides...

Страница 5: ...arm The device supports 2x Liquid Petroleum Gas LPG Sensors and will work with 12V or 24V systems In the box you will have 1 Twin Channel Gas Alarm Main Unit 2 LPG sensors with 3 5m cable 1 User manua...

Страница 6: ...the front panel of your Twin Channel Gas Alarm is the Power Indicator This LED illuminates green when the unit is powered on State Power The unit is power on correctly off There is no power to the uni...

Страница 7: ...first is the ALARM LED and will illuminate red when gas is detected The second is the FAULT LED and will illuminate yellow when a fault is detected The test button can be used to see if the unit alarm...

Страница 8: ...ive limit LPG gases are heavier than air therefore the LPG sensor must be located near to the floor State Channel LED s An OFF LED shows that the channel is operating correctly SOLID yellow FAULT LED...

Страница 9: ...ue Description Supply Voltage 12 24V Supply from your system battery Current Draw Standby 140mA When alarm not sounding Current Draw Alarming 140mA When alarm is sounding Number of sensors 2 Supports...

Страница 10: ...r 24V supply Suitable Installation Locations The main unit should be in a location where the alarm is audible and the LEDs can be seen It must be protected from the elements and the ventilation holes...

Страница 11: ...s into the block Wires are secured using a flat head screwdriver To avoid confusion use wire colours that match the colours in the wiring diagram Be sure to wire the cables through the cable routing h...

Страница 12: ...Positive power supply 2 Negative power supply Common Ground 3 Sensor 1 Positive 4 Sensor 1 Negative 5 Sensor 1 Signal 6 Sensor 2 Positive 7 Sensor 2 Negative 8 Sensor 2 Signal 9 Not Used 10 Not Used 1...

Страница 13: ...ll illuminate and the red LED will flash every second alongside a beeping sound During this time the unit will check for attached sensors and start the initialisation process The initialisation proces...

Страница 14: ...mmediately sound the alarm and illuminate the red LED 2 By allowing a small amount of lighter fluid vapour to pass by the LPG sensors This will test the sensor itself All Twin Channel Gas Alarms and s...

Страница 15: ...he event of an alarm ensure that nothing is used which could ignite gas matches engine ignition etc Ventilate the area by opening doors and hatches Vacate any interior cabins and remain outside until...

Страница 16: ...the sensor Frequent false alarms Contaminated Sensor or other gases present Sensor over 2 years old Replace the sensor Regular beeping while not initialising or Fault light is lit Low supply voltage C...

Страница 17: ...ars as their sensitivity can change over time To replace the LPG sensors 1 Switch off the power supply 2 Remove the top cap from the sensor housing 3 Remove the sensor from the housing 4 Gently insert...

Страница 18: ...the sensors to extreme temperatures below 0 C or above 60 C Handle sensors or unit internals while powered up Connect more than the max number of sensors to the unit DO Replace the sensors after the r...

Страница 19: ...ails Website www envinsci co uk Online Shop www envinsci co uk envin shop Email info envinsci co uk Telephone 44 0 1829 771 792 Address Envin Scientific Limited Technology House Chowley Oak Tattenhall...