MVR-300™ Refrigerant Gas Detector
P/N: 6203-9000 Version 1
37
Reg
Addr
Name
Description
Data Type
Def Val
1019
Gas Low Alarm % FS (0-100)
Low alarm threshold as
percentage of full scale
Unsigned
Integer
1020
Gas High Alarm % FS (0-100)
High alarm threshold as
percentage of full scale
Unsigned
Integer
1021
Minimum Alarm Setting PPM
Lowest allowable alarm setting
Unsigned
integer
1022
Sensor Gas Type Text Char
1,2
Text string indicating the target gas
e.g., "R410a"
ASCII
1023
Sensor Gas Type Text Char
3,4
ASCII
1024
Sensor Gas Type Text Char
5,NULL
ASCII
1025
Main Electronics UID Char
1,2
Text string indicating the detector
serial number e.g., "U1234567"
ASCII
1026
Main Electronics UID Char
3,4
ASCII
1027
Main Electronics UID Char
5,6
ASCII
1028
Main Electronics UID Char
7,8
ASCII
1029
Sensor Module SID Char 1,2
Text string indicating the sensor
serial number e.g., "S7654321"
ASCII
1030
Sensor Module SID Char 3,4
ASCII
1031
Sensor Module SID Char 5,6
ASCII
1032
Sensor Module SID Char 7,8
ASCII
1036
Signed Raw Gas
Concentration PPM - no
thresholding
Raw gas concentration used for
calibration procedure
Signed
integer
1037
Rate of change of sensor
resistance
Rate of change of semiconductor
sensor resistance. Used to
determine stability of gas response
in calibration
Float
1038
1039
Sensor cal gas lower limit
PPM
Lower limit of the gas for
calibration
Unsigned
Integer
1040
Sensor cal gas upper limit
PPM
Upper limit of the gas for
calibration
Unsigned
Integer
1041
Auto Cal Zero Time
Remaining
Seconds remaining in auto zero
calibration procedure
Unsigned
Integer
0
1042
Auto Cal Span Time
Remaining
Seconds remaining in auto span
calibration procedure
Unsigned
Integer
0
1043
Auto Cal Recovery Time
Remaining
Seconds remaining in span
recovery
Unsigned
Integer
0