AB-7358-U
7
Parameter setting screen
Press and hold the [ENT] button to switch to the parameter setting screen from the analog values display screen.
Figure 5. Parameter setting screen
Display area
Display item
1
indicating the parameter setting screen
2 Parameter
number
3
Current setpoint set for the parameter shown in the
display area 2.
4
No item displayed
5
No item displayed
Setting buttons
Function
[
] Cursor button
Press this button to select the digit of the
parameter number and of the setpoint. The
selected digit flashes.
[
] Down button
Press this button to change the selected digit.
[
] Up button
Press this button to change the selected digit.
[ENT] Enter button
Press this button to finally set the changed
parameter.
Press and hold this button to go back to the
analog values display screen.
Note:
No button operation for continuous 10 minutes on the parameter
setting screen will automatically switch from the parameter setting
screen to the analog values display screen.
Error display screen
Figure 6. Error display screen
Display area
Display item
[E] Error
occurred
1
indicating the error display screen
2 Error
code
3
No item displayed
4
No item displayed
5
No item displayed
Setting buttons
Function
[
] Cursor button
Not used in the error display screen.
[
] Down button
Press this button to go back to the analog
values display screen.
[
] Up button
Press this button to go back to the analog
values display screen.
[ENT] Enter button
Not used in the error display screen.
Note:
For details of the error codes, refer to
AB-7363-U Instruction
Manual of ACTIVAL Flow Measurement and Control Valve
Standalone Model
.
Display area 1
Display area 2
Error indicator
Display area 1
Display area 2
Display area 3