AB-7358-U
10
4) Arrange the cable connected to Display Panel.
Cautions for arranging the cable:
Do not pull the cable.
To prevent water from flowing down to Display Panel through the cable, let the cable sag, as Fig. 12 shows.
When installing Display Panel on an AHU side plate, seal the wiring hole on the AHU side plate, as Fig. 12 shows.
Damp or dew condensation may damage the Display Panel, otherwise.
Figure 12. Cable arrangement
5) Film is attached to the front surface (face plate) of Display Panel for protection before shipment. Remove the film before
activating Display Panel.
6) Display Panel is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet.
However, it may possibly be installed outdoors or in a ceiling. In such a case, install the Display Panel as shown in Figs. 13
and 14. Consider the conditions and requirements of your Display Panel installation and decide the location.
Figure 13. Display Panel installed outdoors (in a rainproof box)
Display Panel
Display Panel
Sealing material
Sealing material
Cable
Let the cable sag.
Cable
Let the cable sag.
Cable led out of the rear side of Display Panel
Cable led through the conduit of Display Panel
2" (50 mm) stanchion
Display Panel
in a protection box
Display Panel
in a protection box
directly on a wall
2" (50 mm) stanchion
Display Panel
in a plastic box
(commercially available)