AB-7358-U
6
Items to be displayed on LCD
Analog values such as pressure, flow, and temperature are displayed on the LCD. Setting buttons set/change various
parameters and display error description (when an error occurs). Be sure to enable the parameter setting (Parameter 60) before
changing any parameters. For details, see
AB-7363-U Instruction Manual of ACTIVAL Flow Measurement and Control
Valve Standalone Model
.
Analog values display screen
Analog values display screen appears on the LCD when you turn on the Display Panel.
Figure 4. Analog values display screen
Display area
Description
Display range
Unit
Item
Display Panel connected to:
Range
1
Pvin
Valve inlet pressure
Model FVY5137
0 to 160
psig
Model FVY513E
0 to 320
psig
2
Pvout
Valve outlet pressure
Model FVY5137
0 to 160
psig
Model FVY513E
0 to 320
psig
3
Q
Actual flow
0.000 to 999.9
GPM
4 T
1
Coil inlet temperature
14 to 212
°F
5 T
2
Coil outlet temperature
14 to 212
°F
Opening
Valve position indicated in a bar graph
0 to 100 (with every 10 % increment)
%
Flowrate
Flow indicated in a bar graph
0 to 100 (with every 10 % increment)
%
E
Error occurred ([E] flashes.)
H C
AHU operation mode ([H]: Heat / [C]: Cool)
Setting buttons
Function
[
] Cursor button
Not used in the analog values display screen.
[
] Down button
Press this button to switch to the error display screen when the error indicator [E] flashes.
[
] Up button
Press this button to switch to the error display screen when the error indicator [E] flashes.
[ENT] Enter button
Press and hold this button to switch to the parameter setting screen.
Heat/Cool operation mode
indicator
Display area 1
Enter button
Error indicator
Display area 2
Display area 3
Display area 4
Display area 5
Up button
Down button
Cursor button
Valve position in bar graph
Flow rate in bar graph