AB-7358-U
3
IMPORTANT:
In case an Azbil Corporation product fails, you are required to provide your Equipment with safety design such
as fool-proof design*
1
, and fail-safe design*
2
(anti-flame propagation design, etc.), whereby preventing any
occurrence of physical injuries, fires, significant damage, and so forth. Furthermore, fault avoidance*
3
, fault
tolerance*
4
, or the like should be incorporated so that the said Equipment can satisfy the level of reliability and
safety required for your use.
*1. A design that is safe even if the user makes an error.
*2. A design that is safe even if the device fails.
*3. Avoidance of device failure by using highly reliable components, etc.
*4. The use of redundancy.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Model Number
Model number
Description
QY5010
Base model number of Display Panel for Model FVY513X
S1000S-001 Power supplied from ACTIVAL Flow Measurement and Control Valve standalone model (Model FVY513X)
Specifications
Item Specification
Power supply
12 V DC
1 V (supplied from Model FVY513X)
Power consumption
Max. 0.1 VA
Cable
AWG 22 (0.3 mm
2
) , 4-core cable
Environmental
conditions
Rated operating
condition*
1
Ambient temperature
32
F to 122
F (0
C to 50
C)
Ambient humidity
10 % RH to 85 % RH (non-condensing)
Vibration 19.4
fps
2
(5.9 m/s
2
), 10 Hz to 150 Hz
Transport/storage
conditions
Ambient temperature
-4
F to 158
F (-20
C to 70
C)
Ambient humidity
10 % RH to 85 % RH (non-condensing)
Vibration 32.2
fps
2
(9.8 m/s
2
), 10 Hz to 150 Hz
Enclosure rating
IEC IP40 (dustproof)
Display*
2
Device
Liquid Crystal Display (LCD)
Items to display
Pvin
Valve inlet pressure (psig)
Pvout
Valve outlet pressure (psig)
Q
Actual flow (GPM)
T1
Coil inlet temperature (
F)
T2
Coil outlet temperature (
F)
HC Heat/Cool
E Error
Opening
Actual valve position (% in bar graph)
Flowrate
Actual flow rate (% in bar graph)
Communication Transmission
system AP-bus (RS-485 communication)
Transmission speed
4800 bps
Transmission distance
Max. 164 ft (50 m)
Number of Display Panel
connectable
One per single Model FVY513X
Materials
Case
Modified polyphenylene ether (PPE)
Base plate
Modified polyphenylene ether (PPE)
Face plate
Polyester (PET)
Accessory
- Two tapping screws (M4) for mounting
- Two 'kPa' unit stickers
Weight
0.33 lb (150 g)
Notes:
*1 LCD service life may shorten if Display Panel is used in an environment with high temperature and humidity.
*2 For display accuracy, refer to specification data of Model FVY513X.