background image

AB-7358-U 

 

IMPORTANT: 
 

In case an Azbil Corporation product fails, you are required to provide your Equipment with safety design such 

as fool-proof design*

1

, and fail-safe design*

2

 (anti-flame propagation design, etc.), whereby preventing any 

occurrence of physical injuries, fires, significant damage, and so forth. Furthermore, fault avoidance*

3

, fault 

tolerance*

4

, or the like should be incorporated so that the said Equipment can satisfy the level of reliability and 

safety required for your use. 

 

*1. A design that is safe even if the user makes an error.  
*2. A design that is safe even if the device fails.  
*3. Avoidance of device failure by using highly reliable components, etc.  
*4. The use of redundancy. 

 

Note:  This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of 

the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the 
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency 
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio 
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case 
the user will be required to correct the interference at his own expense. 

 
Model Number 

Model number 

Description 

QY5010 

 

Base model number of Display Panel for Model FVY513X 

 

S1000S-001  Power supplied from ACTIVAL Flow Measurement and Control Valve standalone model (Model FVY513X) 

 

Specifications 

Item Specification 

Power supply 

12 V DC 

 1 V (supplied from Model FVY513X) 

Power consumption 

Max. 0.1 VA 

Cable 

AWG 22 (0.3 mm

2

) , 4-core cable 

Environmental 
conditions 

Rated operating 
condition*

1

 

Ambient temperature 

32 

F to 122 

F (0 

C to 50 

C) 

Ambient humidity 

10 % RH to 85 % RH (non-condensing) 

Vibration 19.4 

fps

2

 (5.9 m/s

2

), 10 Hz to 150 Hz 

Transport/storage 
conditions 

Ambient temperature 

-4 

F to 158 

F (-20 

C to 70 

C) 

Ambient humidity 

10 % RH to 85 % RH (non-condensing) 

Vibration 32.2 

fps

2

 (9.8 m/s

2

), 10 Hz to 150 Hz 

Enclosure rating 

IEC IP40 (dustproof) 

Display*

2

 

Device 

Liquid Crystal Display (LCD) 

Items to display 

Pvin 

Valve inlet pressure (psig) 

Pvout 

Valve outlet pressure (psig) 

Actual flow (GPM) 

T1 

Coil inlet temperature (

F) 

T2 

Coil outlet temperature (

F) 

HC Heat/Cool 
E Error 
Opening 

Actual valve position (% in bar graph) 

Flowrate 

Actual flow rate (% in bar graph) 

Communication Transmission 

system  AP-bus (RS-485 communication) 

Transmission speed 

4800 bps 

Transmission distance 

Max. 164 ft (50 m) 

Number of Display Panel 
connectable 

One per single Model FVY513X 

Materials 

Case 

Modified polyphenylene ether (PPE) 

Base plate 

Modified polyphenylene ether (PPE) 

Face plate 

Polyester (PET) 

Accessory 

- Two tapping screws (M4) for mounting 
- Two 'kPa' unit stickers 

Weight 

0.33 lb (150 g) 

Notes: 
 *1  LCD service life may shorten if Display Panel is used in an environment with high temperature and humidity. 
 *2  For display accuracy, refer to specification data of Model FVY513X. 

Содержание QY5010S1000

Страница 1: ...513X and the valve position at one time Installable 164 ft 50 m away from Model FVY513X Display panel is connected to Model FVY513X with AWG 22 0 3 mm 4 core cable and max cable length is 164 ft 50 m...

Страница 2: ...ion For example the sign on the left notifies that disassembly is prohibited Instructs users to carry out a specific obligatory action to prevent possible danger The symbol inside d graphically indica...

Страница 3: ...se model number of Display Panel for Model FVY513X S1000S 001 Power supplied from ACTIVAL Flow Measurement and Control Valve standalone model Model FVY513X Specifications Item Specification Power supp...

Страница 4: ...lies with the following Electromagnetic Compatibility EMC EMC EN61326 1 Class A Table 2 For use in an industrial electromagnetic environment Dimensions Outside dimensions Figure 1 Outside dimensions M...

Страница 5: ...AB 7358 U 5 Parts Identification Figure 3 Parts identification Hook to remove the case from the base plate Base plate Case Face plate Insertion guide female LCD Insertion guide male...

Страница 6: ...160 psig Model FVY513E 0 to 320 psig 3 Q Actual flow 0 000 to 999 9 GPM 4 T1 Coil inlet temperature 14 to 212 F 5 T2 Coil outlet temperature 14 to 212 F Opening Valve position indicated in a bar grap...

Страница 7: ...to go back to the analog values display screen Note No button operation for continuous 10 minutes on the parameter setting screen will automatically switch from the parameter setting screen to the ana...

Страница 8: ...te and insert stripped lead wires to each terminal Terminals arrangement Figure 7 Sheath strip length Terminal number Type Lead wire color 1 12 V DC Red RED 2 0 V Black BLK 3 AP bus White WHT 4 AP bus...

Страница 9: ...se plate terminals out of the base plate through the base plate conduit on the bottom right and mount the base plate on the mounting location with the two M4 tapping screws accessory of Display Panel...

Страница 10: ...is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet However it may possibly be installed outdoors or in a ceiling In such a case install the...

Страница 11: ...the cable to Model FVY513X refer to Specification Installation of Model FVY513X AB 7350 U ACTIVAL Flow Measurement and Control Valve Standalone Model Models FVY5137J PN10 GG 20 AB 7354 U ACTIVAL Flow...

Страница 12: ...AB 7358 U ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries Rev 3 0 Jun 2016 AB 7358 U 12...

Отзывы: