Azbil Corporation
Calibration
Model PTG71 / 72 - Smart Pressure Transmitter 9-3
9-2 : Calibrating the set range by inputting the actual pressure
Overview
This section describes how to calibrate URV and LRV for the set range by inputting a
reference pressure into the Transmitter using the HART Communicator.
Calibrate the LRV first and then URV.
Calibration devices
Generally, the calibration devices listed below are required:
•
Reference pressure generator : A generator capable of producing pressure over
a range of measurement close to that of the
transmitter to be tested.
•
Accuracy
: ± 0.05% F.S. or ± 0.1% (whichever is larger)
•
Power supply
: 24 V DC
•
Standard resistor
: 250
Ω
±0.005%
•
Voltmeter
: Digital voltmeter (10 V DC range) with an
accuracy of ±0.02% rdg + 1dgt
• HART Communicator
Requirements for calibration
CAUTION
When conducting the actual-pressure calibration, the following requirements must be
satisfied:
• The calibration must be conducted in a testing laboratory where there is no wind.
•
The standard temperature is 23°C {73°F} and the standard humidity is 65%.
Room temperatures from 15°C {59°F} to 35°C {95°F} and room humidity from
45% to 75% are acceptable as long as the result of measurement is not influenced.
• It is best if the accuracy of the measuring instruments to be four times greater
than that of the Transmitter.
Содержание PTG71
Страница 1: ...Smart Pressure Transmitter Model PTG71 72 User s Manual CM2 PTG300 2001...
Страница 12: ...Preface Azbil Corporation x Model PTG71 72 Smart Pressure Transmitter...
Страница 16: ...Table of Contents...
Страница 20: ...Descriptions of Parts Azbil Corporation 1 4 Model PTG71 72 Smart Pressure Transmitter...
Страница 36: ...Azbil Corporation 2 16 Model PTG71 72 Smart Pressure Transmitter...
Страница 42: ...Calibration Azbil Corporation 4 2 Model PTG71 72 Smart Pressure Transmitter...
Страница 78: ...Spare Parts Azbil Corporation 10 2 Model PTG71 72 Smart Pressure Transmitter...
Страница 79: ......
Страница 82: ......
Страница 84: ......